Table Of Basic Menu Parameters; Description Of Basic Menu Parameters - Icar 5LSA Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1.7 TABLE OF BASIC MENU PARAMETERS

PARAMETER 1
P.01
P.02
Smallest step kvar (lowest common multiple)
P.03
P.04
P.05
P.06 (LED 1)
P.06 (LED 2)
Follow the same programming for the re-
maining steps as above for the first two
P.06 (LED n-1)
steps except for the last two.
Penultimate step coefficent.
Follow the same programming for the re-
maining steps as above for the first two
P.06 (LED n)
steps except for the last two.
Last step coefficient.
Setting of required cosϕ value (Ind).
CAUTION! If you have purchased a finished panel, this is the only parameter to be
preset.
n = Number of controller steps.
noA = Normally open contact under no alarm conditions.
ncA = Normally closed contact under no alarm conditions.
FAn = Fan control.
See Measurement and cosϕ setting section on page 34.

1.8 DESCRIPTION OF BASIC MENU PARAMETERS

P.01 - CT primary current
For values higher than 1000, a flashing dot indicates "thousands".
P.02 - Smallest step kvar
Rated power in kvar of the smallest installed capacitor bank.
Example: For 10 kvar, set 10.0
P.03 - Rated capacitor voltage
Rated voltage (nameplate) of the capacitors.
Example: For 460V, set 460
P.04 - Reconnection time of the same step in seconds
Minimum time needed for the capacitor to discharge and be ready to be used again.
Example: For 60 seconds, set 060
P.05 - Sensitivity
The sensitivity is a coefficient, which allows adjusting the controller operating speed. A
low sensitivity provides faster adjustments but with a greater number of switchings. With
high sensitivity, the regulation is slower but with fewer switchings.
The sensitivity value corresponds to the time the controller waits before responding to a
reactive power demand which is equal to the smallest step (kvar). For higher power de-
DESCRIPTION
CT primary current
Rated capacitor voltage (V)
Reconnection time (sec)
Sensitivity (sec)
Step 1 coefficient
Step 2 coefficient
31
RANGE
DEFAULT
OFF... 10.000
0.5... 300
80... 750V
5... 240sec
5... 600sec
0... 16
0... 16
0... 16
noA
ncA
FAn
0... 16
noA
ncA
FAn
0.80Ind...
0.80Cap
OFF
1.00
400
60
60
0
0
0
0
0.95

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

7lsa8bsa12bsa

Table des Matières