Icar 5LSA Notice D'utilisation page 41

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

the default setting.
ALARM
CODE
A01
A02
A03
A04
A05
A06
A07
A08
A09
Note:
None of the above-indicated alarms are non-volatile.
In MANU mode the steps disconnection takes place only for the No voltage release (micro
-breaking) alarm A09 - No-voltage release.
A01 - Under compensation
Capacitors are all connected and cosϕ is lower than the set-point value.
A02 - Over compensation
All capacitors are disconnected and cosϕ is higher than the set-point value.
A03 - Low current
Current value is lower than 2.5% full scale value. In automatic, the capacitors are discon-
nected after 2 minutes of the alarm activation.
A04 - High current
Current value is 120% higher than full scale value.
A05 -Low voltage
Voltage value is -15% lower than lower rated voltage.
A06 - High voltage
Voltage value is +10% higher than higher rated voltage.
A07 - Capacitor overload
Current value flowing in the capacitors is higher than the set threshold (refer to P.20 and
P.21 of advanced menu).
A08 - Overtemperature
Internal temperature value is higher than the set threshold (refer to P.27 of advanced
menu).
A09 - No-voltage release
Voltage failure duration is more than 8ms.
DESCRIPTION
Under compensation
Over compensation
Low current
High current
Low voltage
High voltage
Capacitor overload
Overtemperature
No-voltage release
39
15min
120sec
5sec
120sec
5sec
15min
180sec
30sec
0sec