Toshiba Carrier MMD-AP0726HP-UL Manuel D'installation page 23

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Check method (The following check code table explain in SMMS-e.)
On the wired remote control, central control remote control and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote control) or 7-segment display (on the outdoor interface P.C. board) to display the operation
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with trouble of the air conditioner can be found as shown in the following table.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
In case of check from indoor remote control: See "Wired remote control display" in the list.
In case of check from outdoor unit: See "Outdoor unit 7-segment display" in the list.
In case of check from indoor unit with a wireless remote control: See "Sensor block display of receiving unit" in the list.
Check code
Outdoor unit 7-segment display
Wired remote control
display
E01
E02
E03
E04
E06
E06
No. of indoor units in which sensor has been normally received
E07
E08
E08
Duplicated indoor unit addresses
E09
10
11
01: Indoor/Outdoor units communication
E12
E12
02: Outdoor/Outdoor units communication
E15
E15
00: Capacity over
E16
E16
01 ~: No. of connected units
E18
00: No header
E19
E19
02: Two or more header units
01: Outdoor unit of other line connected
E20
E20
02: Indoor unit of other line connected
02: No header unit
E21
E21
00: Multiple number of header units
E22
E22
E23
E23
E25
E25
E26
E26
No. of outdoor units which received signal normally
E28
E28
Detected outdoor unit number
E31
E31
Number of IPDU (*1)
43-EN
01_1117882101-EN.indd 22
01_1117882101-EN.indd 22
Wireless remote control
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Check code name
Ready
Flash
Communication trouble between indoor unit and remote control
(Detected at remote control side)
Remote control transmission trouble
Communication trouble between indoor unit and remote control
(Detected at indoor unit side)
Communication circuit trouble between indoor/outdoor unit (Detected
at indoor unit side)
Decrease of No. of indoor units
Communication circuit trouble between indoor/outdoor unit (Detected
at outdoor unit side)
Duplicated indoor unit addresses
Duplicated master remote control
Communication trouble between indoor unit MC
Communication trouble between Application control P.C.board and
indoor unit P.C.board.
Automatic address start trouble
No indoor unit during automatic addressing
Capacity over / No. of connected indoor units
Communication trouble between header and follower units Indoor
unit
Outdoor header units quantity trouble
Other line connected during automatic address
Trouble in number of heat recovery header units
Reduction in number of heat recovery units
Sending trouble in communication between outdoor units
Trouble in number of heat recovery units (trouble with reception)
Duplicated follower outdoor addresses
Decrease of No. of connected outdoor units
Follower outdoor unit trouble
IPDU communication trouble
– 22 –
: Lighting,
: Flashing,
: Goes off
IPDU: Intelligent Power Drive Unit
ALT: Flashing is alternately when there are two ashing LED.
SIM: Simultaneous ashing when there are two ashing LED.
Judging device
Remote control
Remote control
Indoor unit
Indoor unit
l/F
l/F
Indoor unit • l/F
Remote control
Indoor unit
Indoor unit
l/F
l/F
l/F
Indoor unit
l/F
l/F
l/F
l/F
l/F
l/F
l/F
l/F
l/F
6/16/2559 BE 8:51 AM
6/16/2559 BE 8:51 AM
EN
EN
EN
EN
EN
EN
EN
EN
44-EN

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Carrier mmd-ap0966hp-ul

Table des Matières