MODBUS CONTROL & INTERFACE FEATURES
UNIT'S SLAVE ADDRESS SETTING
To be able to operate each unit individually, the unique unit's slave address should be set.
Connect the PFW3 remote control to the main electronic board.
Press & hold MODE &
To increase/decrease the setting, press the
The 2-digit LED will blink the new setting for 5 seconds.
MODBUS CONTROL & INTERFACE
The modbus control and interface features can be used via the RS-485 port. A 24 AWG cable is recommended, less than 500m long.
The communication protocol is Modbus RTU with the baud rate of 19200 bps, LSB first + even parity + 1 stop bit.
This PCB operates as a slave unit that can support these below Modbus functions.
01(dec) – Read variable (max 16 variables for a single command) 03(dec) – Read registers (max 16 registers for a single command)
05(dec) – Write single variable
06(dec) – Write single register 15(dec) – Write variables (max 16 variables for a single command)
16(dec) – Write registers (Max 16 registers for a single command)
Address and details of the variables
Address
Hex
Dec
No.
0000
0
1
0001
1
2
Register address & details
Address
Hex
Dec No.
0000 0
1
0001 1
2
0002 2
3
0010 16
17
0011 17
18
0012 19
19
0021 33
34
0022 34
35
0023 35
36
0024 36
37
0025 37
38

SYSTEM FEATURES

7.1 EMERGENCY ON/OFF BUTTON
In case the wireless remote is lost, there is an emergency button on the fan coil unit to turn on/off the air-conditioner and also to
change the operating mode with the sequence below.
buttons for 3 seconds, the 2-digit LED will blink the current address.
or
/ description
USER POWER ON/OFF
USER SWEEP ON/OFF
/ description
USER MODE
USER FAN SPEED LEVEL
USER SET TEMPERATURE (ROOM)
System operating status register#1
System operating mode
System fan speed level
System alarm status
System operating status register#2
Room temperature
Indoor coil temperature
Outdoor coil / Water-in temperature
POWER OFF
POWER OFF
key. The address can be set 1-99 (decimal).
POWER OFF
POWER OFF
POWER OFF
* R = read only, RW = read/write
R/W
RW
RW
* R = Read only , RW = Read/Write
R/W
/ description
RW
0-4 for FAN, COOL, DRY, HEAT, AUTO
RW
0 = Auto speed , 1-3 for level 1-3
RW
180-300 from 18.0 to 30.0°C
R
Bit#0 = Power, Bit#1 = Sweep
R
0-3 for FAN, COOL, DRY, HEAT
R
0 = Off , 1-4 for level 1-4
Bit#0 = Troom-error, #1 = Tindc-error
#2 = Toutc/water-error, #3 = Fan fail Bit#8 = Ind-
freeze, #9 = Out-defrosting
R
#10 = Ind-overheat, #11 = Out-overheat
#14 = Wrong mode water (not cool)
#15 = Wrong mode water (not heat)
Bit#0 = Cool relay, #1 = Ofan/Pump relay
R
#2 = Rev/Heat relay, #3 = Aux relay
R
0-500 for 0.0 to 50.0°C
R
0-500 for 0.0 to 50.0°C
R
0-500 for 0.0 to 50.0°C
POWER ON
COLD
POWER ON
COOL
HEAT
POWER ON
POWER ON
POWER OFF
COLD
COLD
POWER ON
POWER ON
COOL
COOL
HEAT
HEAT