LEGRAND Wattstopper FSP-211 Instructions D'installation page 3

Haut/bas/éteint luminaire avec détecteur irp extérieur intégré
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three rechargeable AAA
NiMH batteries. The battery status displays in the upper right corner of the display. Three bars next
to BAT= indicates a full battery charge. A warning appears on the display when the battery level falls
below a minimum acceptable level. To conserve battery power, the FSIR-100 automatically shuts off
10 minutes after the last key press.
• If communication is not successful, (if possible) move closer to the sensor.
• If still not successful, there may be too much IR interference from other sources. Programming
the unit at night when there is no daylight available may be the only way to communicate with
the sensor.
Navigate from one field to another using (up) or (down) arrow keys. The active field is indicated
by flashing (alternates) between yellow text on black background and black text on yellow
background.
Once active, use the Select button to move to a menu or function within the active field. Value
fields are used to adjust parameter settings. They are shown in "less-than/greater-than" symbols:
<value>. Once active, change them using(left) and(right) arrow keys. The right key increments
and the left key decrements a value. Selections wrap-around if you continue to press the key
beyond maximum or minimum values. Moving away from the value field overwrites the original
value. The Home button takes you to the main menu. The Back button can be thought of as an
undo function. It takes you back one screen. Changes that were in process prior to pressing the
key are lost.
IR communication can be affected by the mounting height of the sensor and high ambient lighting such as
direct daylight or electric light such as floodlights, and some halogen, fluorescent lamps, LED's.
When trying to communicate with the FSP-211, be sure to be positioned under the sensor without any
obstructions. Every time the commissionng tool establishes communication with the FSP-211, the controlled
load will cycle.
Lights will not go to High Mode:
• Check all wire connections and verify the load and the ground wires are tightly secured.
• Make sure that the sensor is not obstructed.
• Check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to simulate darkness
in the room. If the lights come ON, the setpoint needs to be adjusted. If set for minimum, more than 1 fc at the sensor of ambient
light will cause the lights to be held OFF. See the new settings section for instructions.
• If lights still do not turn ON, call 800.879.8585 for technical support.
Lights will not go into Low Mode:
• The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the
desired delay and that there is no movement within the sensor's view for that time period.
• To quickly test the unit operation, enable test mode and move out of the sensor's view. Lights should fade to low mode after 5
seconds.
• If lights still do not fade to Low Mode, call 800.879.8585 for technical support
BATTERIES
NAVIGATION
IR COMMUNICATION
TROUBLESHOOTING
3
Power
BAT=
On/Off
FSP-211
HBP-111
Back
Left
Down
15'-30'
* Distance may vary depending on
the lighting environment
IR tx/rx
Home/Main
Menu
Up
Right/Next
Select

Publicité

Table des Matières
loading

Table des Matières