NOTE Depending on user confi guration, the pins must be shorted or opened to keep the UPS running. To
NOTE Depending on user confi guration, the pins must be shorted or opened to keep the UPS running. To
restart the UPS, reconnect (re-open) the EPO connector pins and turn on the UPS manually. Maximum
restart the UPS, reconnect (re-open) the EPO connector pins and turn on the UPS manually. Maximum
resistance in the shorted loop is 10 ohm.
resistance in the shorted loop is 10 ohm.
NOTE Always test the EPO function before applying your critical load to avoid accidental load loss.
NOTE Always test the EPO function before applying your critical load to avoid accidental load loss.

LOAD SEGMENTS

Load segments are sets of receptacles that can be controlled by power management softwa-
re or through the display, providing an orderly shutdown and startup of your equipment. For
example, during a power outage, you can keep critical equipment running while you turn off other
equipment. This feature allows you to save battery power.
Each UPS has two load segments:
• Load Segment 1: The power shedding battery voltage of this segment can be set by LCD.
• Load Segment 2.
UPSILON2000 POWER MANAGEMENT SOFTWARE
Each UPS ships with UPSilon2000 Power Management Software. To begin installing UPSilon2000 software, see the
instructions accompanying the Software Suite CD.
NOTE Install UPSilon2000 power management software with the serial number attched on the cover of the
NOTE Install UPSilon2000 power management software with the serial number attched on the cover of the
CD.When running the monitor software , choose appropriate communication port. If using RS232, choose
CD.When running the monitor software , choose appropriate communication port. If using RS232, choose
COM1/2 and Megatec protocol. If using USB, choose megatec USB.
COM1/2 and Megatec protocol. If using USB, choose megatec USB.
UPSilon2000 software provides up-to-date graphics of UPS power and system data and power fl ow. It also gives
you a complete record of critical power events, and it notifi es you of important UPS or power information. If there is
a power outage and the UPS battery power becomes low, UPSilon2000 software can automatically shut down your
computer system to protect your data before the UPS shutdown occurs.

6 UPS Maintenance

This section explains how to:
• Care for the UPS and batteries
• Replace Extended Battery Packs (EBPs)
• Test new batteries
• Recycle used batteries or UPS

UPS AND BATTERY CARE

For the best preventive maintenance, keep the area around the UPS clean and dust‐free. If the atmosphere is very
dusty, clean the outside of the system with a vacuum cleaner. For full battery life, keep the UPS at an ambient tempe-
rature of 25°C (77°F).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service life varies, de-
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service life varies, de-
pending on the frequency of usage and ambient temperature. Batteries used beyond expected service life
pending on the frequency of usage and ambient temperature. Batteries used beyond expected service life
will often have severely reduced runtimes. Replace batteries at least every 5 years to keep units running at
will often have severely reduced runtimes. Replace batteries at least every 5 years to keep units running at
peak effi ciency.
peak effi ciency.
STORING THE UPS AND BATTERIES
If you store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The
internal batteries charge to 80% capacity in less than 5 hours. However, we recommends that the batteries charge for
FIG 24 Load Segments