Green Cell 1KVAS-EBP Mode D'emploi page 19

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

lect the numerical value in accordance with "OPU" function. The provided voltages are 208v, 220v, 230v, 240,you
can choose any one of them by yourself (The default is 220v).
3. Confi rm the output voltage selecting interface. After selecting numerical value, press and hold the function set-
ting key
for more than half a second (less than 2 seconds). Now, the OPU setting function is completed and
the numerical value below the "OPU" will light without fl ashing.
4. Exit from the setting interface. Press and hold function setting key
seconds), exit from the setting interface and return to main interface.
BATTERY PACK (EBP)NUMBER AND TYPE SETTING (4)
1. Enter the setting interface. Press and hold the function setting key
more than 2 seconds, then come to setting interface, Press and hold the
scroll keyfor more than half a second (less than 2 seconds), select the
function setting, choose battery setting interface, at the moment, the letters
"bAt" will fl ash.
2. Enter the battery setting interface. Press and hold the function setting key
for more than half a second (less than 2 seconds), then come to setting
interface of battery, the letters "bAt" will stop fl ashing. The numerical value
below the "bAt" will fl ash. Press and hold the scroll keyfor more than half
a second (less than 2 seconds), select the numerical value in accordance
with the real connected battery strings.
3. Confi rm the battery strings setting interface. After selecting numerical value,
press and hold the function setting key
than 2 seconds). Now, the battery strings setting is confi rmed and the battery type value below will fl ash
4. Set the battery type in the same way.
5. Exit from the setting interface. Press and hold function setting key
seconds), exit from the setting interface and return to main interface.
LOAD SEGMENT SETTING(5)
1. Enter the setting interface. Press and hold the function setting key
than 2 seconds, then come to setting interface, Press and hold the scroll keyfor
more than half a second (less than 2 seconds), select the function setting,
choose battery setting interface, at the moment, the letters "Seg 1" will fl ash.
2. Enter the load segment setting interface. Press and hold the function setting
key
for more than half a second (less than 2 seconds), then come to
setting interface of load segment, the letters "Seg 1" will stop fl ashing. The
numerical value below the "Seg 1" will fl ash. Press and hold the scroll keyfor
more than half a second (less than 2 seconds), select the battery voltage, 10.5v
11.0v 11.5v (default is 10.5v)
3. Confi rm the power shedding shielding battery voltage setting. After selecting
numerical value, press and hold the function setting key
a second (less than 2 seconds). Now, the load shielding battery voltage setting is confi rmed.
4. Exit from the setting interface. Press and hold function setting key
seconds), exit from the setting interface and return to main interface.
EPO INPUT POLARITY SETTING(6)
1. Enter the setting interface. Press and hold the function setting key
than 2 seconds, then come to setting interface, Press and hold the scroll keyfor
more than half a second (less than 2 seconds), select the function setting, cho-
ose EPO Input polarity setting interface, the letters "EPO" will fl ash.
2. Enter the EPO Input Polarity setting interface. Press and hold the function setting
key
for more than half a second (less than 2 seconds) , the letters "EPO" will
stop fl ashing. The letters below the "EPO" will fl ash. Press and hold the scroll
keyfor more than half a second (less than 2 seconds), select the EPO input
polarity, "+P" (open circuit execute EPO function) or "–P" (short circuit execute
EPO function)
3. Confi rm the setting. After selecting EPO input polarity, press and hold the func-
tion setting key
for more than half a second (less than 2 seconds). Now, the setting is confi rmed.
4. Exit from the setting interface. Press and hold function setting key
seconds), exit from the setting interface and return to main interface.
for more than half a second (less
for more than half
for more than half a second (less than 2
for
for more than half a second (less than 2
for more
for more than half a second (less than 2
for more
for more than half a second (less than 2
EN / 19

Publicité

Table des Matières
loading

Table des Matières