2 INTRODUCTION
This multiposition Category IV condensing furnace is
CSA design certified direct vent (2 pipes) or non-direct
vent (1 pipe). The furnace is factory shipped for use
with natural gas. The furnace can be converted in the
field for use with propane gas when a factory supplied
conversion kit is used. Refer to the furnace rating plate
for conversion kit information and part list table
This furnace is designed for minimum continuous return
air temperature of 60 °F (16 °C) or intermittent operation
down to 55 °F (13 °C) such as when used with a
night setback thermostat. Return air temperature must
not exceed 80 °F (27 °C). Failure to follow these
return air temperature limits may affect reliability of heat
exchangers, motors, and controls.
The furnace should be sized to provide at least 100
% of the design heating load requirement.
load estimates can be made using approved methods
available from Air Conditioning Contractors of America
(Manual J); American Society of Heating, Refrigerating,
and Air Conditioning Engineers; or other approved
engineering methods.
Excessive over sizing of the
furnace could cause the furnace and/or vent to fail
prematurely.
2.1 CODES AND STANDARDS
Follow all national and local codes and standards in
addition to these instructions.
comply with regulations of the serving gas supplier, local
building, heating, plumbing, and other codes. In absence
of local codes, the installation must comply with the
national codes listed below and all authorities having
jurisdiction. In the United States and Canada, follow all
codes and standards for the following:
Heating
The installation must
6
Table 1 – Codes and Standards
TOPIC
USA
Safety
National Fuel Gas Code
(NFGC)
2009/ANSI
the Installation Standards,
Warm
Air
Air Conditioning Systems
ANSI/NFPA 90B
General
NFGC and the NFPA 90B.
installation
For copies,
National
Fire
Association Inc.,
march Park, Quincy, MA
02269; or for only the NFGC
contact the American Gas
Association, 400 N. Capitol,
N.W.,Washington DC 20001
Combustion
and
Section
9.3
and air ventilation
NFPA54/ANSI
Air for Combustion and
Ventilation
Duct systems
Air Conditioning Contractors Association (ACCA) (Manual
D), Sheet Metal and Air Conditioning Contractors National
Association (SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE).
Acoustical
lining
current edition of SMACNA, NFPA 90B as tested by UL Standard
and fibrous glass
181 for Class I Rigid Air Ducts.
duct
Gas
piping
and
NFPA
54/ANSI
pipe
pressure
NFGC; Chapters 5, 6, 7,
testing
and 8 and national plumbing
codes.
Manufactured
Manufactured
Mobile housing
Construction
Standard, Title 24 CFR,
Part 3280 or The Standard
for
Manufactured
Installations
A225.1
Electrical
National
Electrical
connections
(NEC) ANSI/NFPA 70
Venting
Part
7,
equipment, latest edition of
the National Fuel Gas Code
NPFA 54, 90A and 90B
ANSI Z223.1-
IN THE STATE OF MASSACHUSETTS:
• This product must be installed by a
licensed plumber of gas fitter;
• When flexible connectors are used, the
maximum length shall not exceed 36 in.
(914 mm);
• When lever type gas shutoffs are used
they shall be "T" handle type;
• The use of copper tubing for gas
piping is not approved by the state of
Massachusetts;
CANADA
National
Standard
NFPA
54-
Canada, Natural Gas and
Z223.1
and
Propane Installation Code
(NSCNGPIC)
CAN/CSA
Heating
and
B149.1
NSCNGPIC. For a copy,
contact the
contact
Standard
Protection
CSA
International,
Battery
Rexdale
Boulevard,
Etobicoke
(Toronto),
Ontario, M9W 1R3, Canada
of
the
Part 8 of the CAN/CSA
Z223.1
B149.1, Venting Systems
and
Air
Supply
Appliances
Z223.1
CAN/CSA-B149.1, Part 6
Home
Canadian
Standard
and
Safety
Series M92 Mobile Homes,
CAN/CSA Z240MH
Home
ANSI/NCS
Code
Canadian Electrical Code
CSA C22.1
Venting
of
CAN/CSA-B149.1-05 latest
edition
of
Sales,
178
for
for