11. Si une pompe a condensat doit être utilisée,
assurez-vous qu'elle soit compatible avec le
condensat acide.
3.2.2 Downflow multiposition pressure
switch connection
The 3/16" stub just beside the drain of the condensate
box must be drilled or cut open. Use the supplied black
squared PVC tubing to connect the pressure switch (-0.2
in. w.c.) to this stub. (see figure 5)
The pressure switch must also be electrically connected
in series with the low fire pressure switch (top) using the
brown jumper provided in the parts bag. Refer to figure 4
for more details.
Figure 4 –
Downflow position pressure switch
assembly
Figure 5 – Connecting pressure switch in downflow
position
3.3 HORIZONTAL RIGHT
Figure 6 – Horizontal right position
Figure 7 – Horizontal right slope
When installing the furnace in horizontal right position,
make sure the furnace is tilted foward to make it drain
properly. Refer to figure 7.
Plan your installation and make sure you have sufficient
space for the drain trap and exhaust pipe drainage. Drain
trap will add approximately 6.50" to the furnace width.
Refer to figure 6.
3.3.1 Horizontal right condensate drain
trap connection
REFER TO FIGURE 6 FOR INSTALLATION DETAILS
1. Remove all condensate tubings from the inducer
blower and vent collector. Block the openings with
provided 5/8" and 1/2" black caps.
2. Remove the horizontal right drain trap knock-out.