Télécharger Imprimer la page

Samsung AE090JXEDEH Manuel D'installation page 17

Masquer les pouces Voir aussi pour AE090JXEDEH:

Publicité

Connecting the cable
Power cable specifications
1 phase
Outdoor unit
AE090JXEDEH
AE120JXEDEH
AE140JXEDEH
AE160JXEDEH
f The power cable is not supplied with Air to Water Heat pump .
f
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
f
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f This Equipment complies with IEC 61000-3-12 .
f
3 Phase
Outdoor unit
AE090JXEDGH
AE120JXEDGH
AE140JXEDGH
AE160JXEDGH
f The power cable is not supplied with Air to Water Heat pump .
f
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (Code
f
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
f This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
f
3 . 3 [MVA] at the interface point between the user's supply and the public system . It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3 . 3 [MVA] .
Rated
Hz
Volts
Min
50
220-240
198
50
220-240
198
50
220-240
198
50
220-240
198
Rated
Hz
Volts
Min
50
380-415
342
50
380-415
342
50
380-415
342
50
380-415
342
ENGLISH-17
Voltage Range
Max
Min. Circuit Amps.
264
264
264
264
Voltage Range
Max
Min. Circuit Amps.
457
457
457
457
MCA
MFA
Max. Fuse Amps.
22 A
27 . 5 A
28 A
35 A
30 A
37 . 5 A
32 A
40 A
MCA
MFA
Max. Fuse Amps.
10 A
16 . 1 A
10 A
16 . 1 A
11 A
16 . 1 A
12 A
16 . 1 A