Eliectrictli connexiona
The maximum total electric power of the complete product is 16KW.
It is necessary to connect each DUO generator to a three-phase 400V mains supply line. It is desirable
to use 2 separate lines. Each of the 2 power lines will be protected by an individual circuit breaker
(with 30mA differential).
We recommend 2 mains cables H07RN-F-5G-2.5 with a conductor section of 2.5MM².
The maximum electric power of each generator is 8KW. The maximum electric currents consumed by
each
generator
It is possible to use for each of the 2 supply lines, a circuit breaker rated at 16Aeff.
(!) We recommend for etch generttor, the uae of t power cord H07RN-F-
It ia eaaentitli thtt the power auppliy liine uaed ia protected by t 30mA
The mains power connection is made at the rear of the generator. The protective cover of the mains
terminal block (2 screws to be unscrewed) must be removed to gain access to the terminal block screws.
Rear view of generator
When the 5 conductors equipped with wiring ends are connected to the terminal block and the 5 terminal
block clamping screws are properly tightened, the protective cover must be fitted with its 2 fixing screws.
in the event that the generator units should be disconnected from the electrical network, it is necessary
to provide means of disconnection from the sector accessible by the user, near the product. If the discon-
nection device is manually operated, it must guarantee total disconnection of the generator, vis-à-vis the
2 phase conductors + the neutral conductor of the electrical network.
on
each
of
the
5G-2.5 (conductor aectiona of 2.5mm²)
differentitli circuit bretker.
3
phases
L1
/
L2
/
L3
is
L1
L2
L3
N
PE
12A.
25