EVENT
DIP 1 ON (hold-to-run mode)
Or failure of a safety device
DIP 2 ON (stroke programming)
Programming sequence stopped due to intervention of a safety
device
EVENT
No transmitter code entered
DIP 1 ON > DIP 2 ON - transmitter code programming for full
opening
DIP 1 ON > DIP 2 ON > DIP 3 ON - transmitter code programming for
R-AUX relay
Correct transmitter codes programming for opening and R-AUX
relay
Remote control code not present in memory
Memory saturated by remote control codes (1000 codes saved)
Radio code deletion for opening and R-AUX relay
EVENT
Stop button pressed
Photocell intervention
Edge intervention
Failure of a safety device or safety device engaged for too long
Alarm from edge
Failed photocells auto-test alarm
Functional block activated by smartphone
Achievement of set cycles
Energy saving activated by smartphone
Alarm - no limit switches reached or unlocked barrier
FAULT
After having carried out the various connections and having supplied
voltage, all the LEDS are switched OFF.
The motor opens and closes, but it has no strength and moves slowly.
The gate opens but does not close after the time set.
The gate does not close by activating the various START, RADIO and
CLOSE buttons.
By activating the START, OPEN or CLOSE button the barrier does not
move.
The slowing phase is not performed.
TABLE SUMMARISING VISUAL AND SOUND ALARMS
SIGNALS DURING PROGRAMMING SEQUENCE
BUZZER STATUS
OFF
OFF
10 s tone with 2 s pause
BUZZER STATUS
OFF
OFF
OFF
1 Tone
OFF
OFF
2 Tones
WARNING SIGNALS DURING OPERATION
BUZZER STATUS
OFF
1 Tone
2 Tones
OFF
2 Tones every 5 s for 1 minute
(It is renewed by giving a command)
4 Tones every 5 s for 1 minute
(It is renewed by giving a command)
OFF
6 Tones every 5 s
(It is renewed by giving a command)
OFF
5 Tones
On the board there are resettable fuses which intervene in the event of a short circuit, interrupting the output
assigned to them.
In the event of troubleshooting, it is advisable to disconnect all the removable connectors and insert them one at a
time in order to more easily identify the cause of the fault.
Check the integrity of fuse F1.
In case of interrupted fuse use only of adequate value
F1 = T 5A Fuse for motor protection
Check trimmers LOW SPEED OPEN and LOW SPEED CLOSE adjustment.
Make sure that the TCA trimmer is activated with LED DL11 ON.
B.I.O. contact always on / green led on => check the status of the clock connected to B.I.O. input.
Photocells Auto-test failed => check the connections between the control panel and the photocells.
Faulty safety edge contact. Faulty photocells contact => Fix or replace the faulty contact.
Photocells Auto-test failed => check the connections between the control panel and the photocells.
START, OPEN or CLOSE command always active.
Check and replace any buttons or micro-switches of the selector switch.
Check LOW SPEED OPEN e LOW SPEED CLOSE trimmers adjustment.
43
FLASHER STATUS
OFF
Flashes ON/OFF 250 ms
OFF
Flashes ON/OFF 500 ms
OFF
On steady
FLASHER STATUS
OFF
Flashes red/green
OFF
Flashes red for 10 s
OFF
Flashes orange for 10 s
OFF
Turns green once
OFF
Turns red once
OFF
Runs 6 green flashes
OFF
Runs 2 green flashes
FLASHER STATUS
LED STATUS AND SIGNAL OUTPUT
OFF
Led DL6 turns OFF
OFF
Led DL7-8 turns OFF
OFF
Led DL9 turns OFF
OFF
Led DL1 flashes ON/OFF 250 ms
Flashes for 1 minute
No led combined
OFF
No led combined
OFF
Led DL12 is steady on green.
OFF
No leds matched
OFF
Blue led flashes once every 5 s
Flashes for 1 minute
No leds matched
SOLUTION
G
B
DL1 LED STATUS
DL12 LED STATUS