ELECTRONIC THERMOSTATS
1.1 Configuration
Status indicator lights
Temperature control knob
Mode selector
i
Read these instructions
carefully before using
the radiator.
2.1 Safety instructions
The installation must comply with current
!
norms and best trade practice in the
country where it is fitted.
The thermostat is class II and protected
against water splashes. It can be installed in
Zone 2 and 3 in bathrooms. Do not touch
thermostat when in the shower or bath.
Install a calibrated earth-leak circuit breaker in
accordance with current norms.
22
CYCLOPE
Radio-controlled thermostat
User instructions
®
3.1 Installation
3.1.1 Where to install it
The thermostat must be installed in
accordance with the diagram:
Shelf
OK!
Do not cover the ventilation holes on
!
the thermostat.
3.1.2 Connecting to the electric power supply
Connect the thermostat's electric wires to the
mains power supply using a junction box. Place
the junction box at least 25cm above the floor.
Install the junction box behind the thermostat.
Do not place any plug sockets or plugs
between the two.
Brown
Light blue/grey Neutral
Black
The power supply circuit must be sectioned.
!
Sectioning must be done using a multi-polar
device sectioning all the power supply
terminals. The sectioning distance between
the contacts of each terminal must be at
least 3mm.
NO!
Live
230 V 50 Hz
Pilot wire External control
(see 5.1)