AMBÉLIA AND JAVA ALUMINIUM
ELECTRIC RADIATOR INSTALLATION
■ ELECTRICAL INSTALLATION
1- The electric installation must be in conformity with the
standards and the code of practice currently used in the
country where the product is going to be installed.
2- The radiator electrical connection must be carried out in
a standardized junction box. In kitchen or bathrooms, the
connection box should be installed 25 cm above the
floor.
3- The radiator must be supplied with 230 V- 50 Hz single-
phase and neutral. Other power supplies cannot be used
the one previously specified.
4- Each radiator must be supplied with a dedicated wire
and protected with a 10 amp circuit breaker for devices
from 500 W to 2000 W of power.
INSTRUCTIONS
■ INSTALLATION RULES
ELECTRIC RADIATORS IN THE WET ROOMS
(kitchens, bathrooms...).
control unit can be touched by the people using the
bath-tub or the shower.
• It must necessarily be connected to the electrical supply
network in a standardized junction box without the using a
socket-outlet. Earthing is prohibited.
• The circuits supplying the electrical devices in the wet
rooms must necessarily be protected by a 30milli amp
Residual Current Device for safe operation.
• This radiator is "class II"
with double insulation
It is "IP24" therefore
protected from splashed
water.
0,60 m
• It can be installed in
0,60 m
0,60 m
bathrooms volume 2 and
3 provided that no electric
.
17