Menus supplémentaires de configuration de source pour la source d'urgence seulement :
62
Section 4 Configuration
Set Emergency Source
Back
B
Y
"
suite de la page précédente
B
Emergency Source
Set Under Frequency
Pickup
B
Y
"
Emergency Source
Set Under Frequency
Dropout
B
Y
"
Emergency Source
Set Over Frequency
Pickup
B
Y
"
Emergency Source
Set Over Frequency
Dropout
B
Y
"
Emergency Source
Set Freq Debounce
B
Y
"
Pickup
??? % of Nominal
80--95%
Back
Dropout
??? % of Pickup
95--99%
Back
Pickup
??? % of Nominal
105--120%
Back
Dropout
??? % of Pickup
101--115% Nominal
Back
Debounce Time
?.? Seconds
0.1 -- 15.0 Seconds
Back