NSPECT NG EXTERNAL ELECTR CAL PARTS
Check to see that the LED is either on or blinking.
LEDs are divided between those for A cycle and those for B cycle. This is determined by either an A or a B appearing in the
circuit code, for example LD301A or LD301B.
Carry out inspections by examining the on/ blinking status of LEDs 301-304.
LED number
LD301
LD302
Name
Diagnosis
Diagnosis
lamp 1
lamp 2
Case 1
Off
Case 2
Blinks once
Case 3
Blinks
Case 4
On
Blinks
Case 5
Off
(blinks once)
Case 6
Off
Case 7
On
Case 8
Off
Case 9
On
All manuals and user guides at all-guides.com
LD303
LD304
Communications
Operation
lamp
lamp
Off
Off
Off
Off
Off
Off
Off
Off
Blinks
Off (blinks)
Off
Off
On
Off
Off
On
On
Off
On
On
Off
On
COMPRESSOR
COMPRESSOR
SIDE  A.
SIDE  B.
L
L
L
L
L
L
L
L
D
D
D
D
D
D
D
D
3
3
3
3
3
3
3
3
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
A
A
A
A
B
B
B
B
SERVICE  SWITCH
C1D1
INDOOR  1
- 324 -
Status
Normal off status or
Off
unconnected
microcomputer power
source
Off
Microcomputer reset
status (immediately
after inserting power
source or immediately
after power source
abnormally)
Off
Abnormally stop
Thermistor abnormally
Off
Communications error
Normal operation
OVL1 operation
OVL2 operation
OVL3 operation
C2D2
C3D3
C4D4
L
N
INDOOR  2
INDOOR  3
INDOOR  4
Checkpoints
If the LED is not on even when the
power
source
is
connected,
the
microcomputer
power
source
unconnected.
Inspection method 1
It is normal for LD301 to blink once
after the power source has been
inserted. If the unit stops when it is in
operation and LD301 blinks once, it is
possible that the power source has
been
temporarily
interrupted
lightening or for some other reason.
Replace the control PCB if this occurs
frequently.
Abnormally stop is shown by the
number of times the LED blinks.
Inspection method 2
Thermistor abnormally is shown by
the number of times the LED blinks.
Inspection method 3
Communications error is shown
by the number of times the LED
blinks.
Inspection method 4
*In the case that an internal unit is
not connected, the number of
connected
internal
units
shown by the number of times
the LED blinks. This is not a
abnormally. The internal unit
has no communications error
and is able to operate normally.
Normal operation
Normal operation
Normal operation
Normal operation
is
by
is