Télécharger Imprimer la page

Hitachi RAF-25NH5 Instructions De Service page 24

Publicité

Les langues disponibles

Les langues disponibles

2. Refrigerant Piping Materials
1) Thickness of Refrigerant Piping
Although the thickness is same as
that for HCFC-22 model, as R410A
model features higher pressure, be
sure to confirm the thickness prior to
use.
Do not use thin pipes
0.7 mm).
2) Flare's Expansion Pipe
The projection when the new flare
tool is used, is as follows.
using the conventional flare tool, be
sure to secure the following projection
by using a gauge for projection
adjustment.
When using the conventional flare
tool, use a gauge for projection
adjustment.
3) Flare Nut Dimensions
Along with changes in the expansion
pipe dimensions, the opposite side
dimensions of flare nuts whose
nominal diameter is 1/2 change so
that different torque wrenches must
be used.
Figures in
) denote those for
HCFC-22.
All manuals and user guides at all-guides.com
thinner than
When
- 24 -
Nominal
Outside
diameter
diameter mm)
1/4
6.35
1/2
12.70
Projection "A" mm) for Flare Tool for R410A
Clutch Type)
1/4: 0-0.5
1/2: 0-0.5
Nominal
Opposite Side Dimensions
diameter
of Flare Nuts for R410A
1/4
3/8
1/2
Thickness
mm)
0.8
0.8
mm)
17 17)
22 22)
26 24)

Publicité

loading