EFROST
Reversing valve defrost system is employed: it consists of balancing period
(1) efrost start condition
When all the following conditions are established, defrost is executed:
Normal operation
   ①
Heat exchange temperature is within defrost range specified by outdoor temperature and heat exchange temperature.
   ②
efrost inhibit period linked to outdoor temperature has passed.
   ③
(2) efrost release condition
If any one of the following conditions is established, defrost is released:
Heat exchange temperature returns (heat exchange temperature
   ①
efrost max time of 12 minutes has elapsed.
   ②
Released by condition
condition (ASTUS=0).
Released by condition
(3) Outputs during defrost
Indoor defrost request: Transmitted to all units being operated in heating mode.
Compressor : Balancing period for [T F414] seconds
[TSKTM2] seconds
period until defrost MAX speed [ EFMAX] is reached
Electric expansion valve
Unit being stopped : [FULL CLOSE] 30 seconds after balancing period has passed
  
Unit being operated : [ FCTPS] 30 seconds before balancing period is finished
  
All manuals and user guides at all-guides.com
during balancing period: When remaining balancing period has elapsed, returned to initial
or
during reversing cycle period: [T F415] Shifted to balancing period.
Accelerating by [ FSTEP]min
reversing cycle period
[PCLOSH$] 15 seconds before balancing period is finished
of rotation speed of compressor, opened by [ FSPPS] pulses and reaches MAX opening
degree [ EFSMX] when rotation speed of compressor reaches [ EFMAX].
- 222 -
reversing cycle period
EFOFF).
Starting of reversing cycle period by [S RCT2] min
/[T FSPT] seconds in remaining reversing cycle
-1
Balancing period for [T F415] seconds
balancing period.
for
-1
[FULL CLOSE] during
Synchronized with step-up