Rating Plate; Date Of Manufacture - Siemens 6SE7087-8KN50 Instructions De Service

Simovert masterdrives; chassis; onduleur (dc-ac) forme encastrable
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

08.2008
NOTE

Rating plate

Date of manufacture

Siemens AG
6SE7087-7KN50
SIMOVERT MASTERDRIVES
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 40 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Altitude: 3000 m
Ambient temperature: 35 °C
⇒ Total derating = 0.845 x 1.125 = 0.95
Fig. 11-2
Rating plate
The date of manufacture can be derived as follows:
Character
Year of manufacture:
U
V
W
X
Table 11-2
Assignment of characters to the month and year of manufacture
Operating Instructions
x Derating
altitude
ambient temperature
K
K
Character
2006
1 to 9
2007
O
2008
N
2009
D
Technical Data
= 0.845
1
= 1.125
2
Unit designation
List of unit options
Year of manufacture
Month of manufacture
Month of manufacture
January to September
October
November
December
11-3

Publicité

Chapitres

Table des Matières
loading

Table des Matières