9.2.1. Constant pressure mode with single
transducer (absolute or differential)
This configuration uses a feedback given by a
pressure transducer (connected as shown in
section 6.7).
Parameters to programm or check (recommended
sequence):
Par.
Description
AP01
Maximum pump pressure
AP02
Primary transducer supply
Primary transducer
AP03
measuring unit
Primary transducer
AP04
minimum value
Primary transducer
AP05
maximum value
UP02
Nominal pump current
UP03
Nominal pump frequency
UP05
Operating mode
UP06
Primary set-point
9.2.2. Constant pressure mode with 2 pressure
transducers (differential mode)
If it is required to use a differential pressure
feedback, between delivery and suction of the pump
by using 2 transducers it's necessary to connect
the first transducer and the second transducer as
shown in section 6.7.
Parameters to programm or check (recommended
sequence):
Par.
Description
AP01
Maximum pump pressure
AP02
Primary transducer supply
Primary transducer
AP03
measuring unit
Primary transducer
AP04
minimum value
Primary transducer
AP05
maximum value
Secondary transducer
AP06
supply
Secondary transducer
AP07
measuring unit
Secondary transducer
AP08
minimum value
Secondary transducer
AP09
maximum value
AP10
Secondary transducer mode
UP02
Nominal pump current
UP03
Nominal pump frequency
UP05
Operating mode
UP06
Primary set-point
To ensure the system works properly, the
primary transducer (B1-B4 clamps) must be
always connected to the delivery pipe, and
the secondary transducer (B5-B8 clamps)
must be always connected to the suction
pipe.
I-MAT_Ed7 - Operating Instructions
9.2.3. Minimum
The frequency converter is equipped with an
automatic stop system in case of low water. In
the case where the system does not guarantee
the correct stop of the pump, it is possible to set
manually the following values:
Frequency before stop
Suggested value
Minimum run frequency
based on pump type
In order to manually set these parameters it is
data sheet
transducer
necessary to change the value of parameter AP17
1 [bar]
from "Auto" to "Man". Then the pre-pause frequency
values (PC02 and PC04 parameters) and the
data sheet
transducer
minimum frequency values (PC01 and PC03
parameters), must be set using the calculation
data sheet
transducer
formulas described in the next section.
see motor plate
9.2.4. Frequency before stop and minimum run
see motor plate
PC
Adjusting the pre-pause frequency (PC02 and
on demand [bar]
PC04 parameters) allows you to properly stop the
pump when the water demand is low and the pump
operation is no longer required (e.g. a leakage or a
small flow of a few liter per minute).
In this case the pump must be stopped for some
seconds and the flow is guaranteed by the reserve
stored in the vessel.
The frequency before stop Hz P can be calculated
as follows:
50 Hz pumps
60 Hz pumps
where: - H set is the working pressure in bar
Suggested value
based on pump type
data sheet
transducer
(*) For the maximum pump pressure it's required:
1 [bar]
For the pumps operating with suction lift subtract
the suction lift value (in bar).
data sheet
transducer
For the pumps installed with suction positive add
the positive suction head value (in bar).
data sheet
transducer
The minimum run frequency (PC01 and PC03
data sheet
transducer
parameters) must be set 6-7 Hz lower than the
frequency before stop.
1 [bar]
data sheet
transducer
9.3. Proportional pressure mode
The proportional pressure operating mode reduce
data sheet
transducer
the pressure proportionally with the water demand
DiFF
of the system.
In this operating mode the frequency converter
see motor plate
keeps a set-point pressure at the maximum
see motor plate
frequency, this set-point pressure could be set with
PC
the parameter UP06.
on demand [bar]
The slope of the pressure-flow rate line could be
set through the percentage of the pressure when
flow is equal to 0.
It is possible to have different configurations of this
operating mode related with the different types and
number of transducers installed:
Proportional pressure with 1 pressure transducer
(absolute or differential transducer).
Proportional pressure with 2 pressure transducers
in differential mode.
run
frequency
pause frequency settings
frequency calculation formulas
Hz=2+ √(Hset÷Hmax )x 50 (*)
Hz=2+ √(Hset÷Hmax )x 60 (*)
- H max is the maximum pump pressure, in
bar, when flow is equal to 0.
and
pre-
EN
Page 39 / 164