1. NAME OF PARTS

RPK-0.8~2.0FSNM "SUMMIT"
RPK-2.5~4.0FSNM "S.B.F"

2. UNITS INSTALLATION

WARNING:
Check to ensure that the accessories are packed with
-
the indoor unit.
Do not install the indoor units outdoors. If installed
-
outdoors, an electric hazard or electric leakage will
occur.
Consider the air distribution from each indoor unit to
-
the space of the room, and select a suitable location
so that uniform air temperature in the room can be
obtained.
The installation height of indoor unit must be 2.3m or
-
more.
No. Part Name
1
Fan
2
Fan Motor
3
Heat exchanger
4
Strainer
5
Distributor
6
Expansion Valve
7
Electrical Box
8
Bearing
9
Refrigerant Gas Pipe Connection
10 Refrigerant Liquid Pipe Connection
11 Drain Hose Connection
12 Auto - Swing Motor
13 Drain Pan
14 Air Filter
15 Air Outlet
16 Air Inlet Grille
17 Wireless Receiver
No. Part Name
1
Fan
2
Fan Motor
3
Heat exchanger
4
Strainer
5
Distributor
6
Expansion Valve
7
Electrical Box
8
Bearing
9
Refrigerant Gas Pipe Connection
10 Refrigerant Liquid Pipe Connection
11 Drain Hose Connection
12 Auto - Swing Motor
13 Drain Pan
14 Air Filter
15 Air Outlet
16 Air Inlet Grille
17 Wireless Receiver
Pay attention to the following points when the indoor
-
units are installed in a hospital or other places where
there are electronic waves from medical equipment,
etc.
Do not install the indoor units where electromagnetic
-
wave is directly radiated to the electrical box, remote
control cable or remote control switch.
Prepare a steel box and install the remote control
-
switch in it. Prepare a steel conduit tube and wire the
remote control cable in it. Then connect the ground
wire with the box and tube.
Install a noise filter when the power supply emits
-
harmful noises..
1
NAME OF PARTS