Fig. 11
Rear Heat Shield to reduce clearance
Single wall pipe, top exit only
B
A: 21" - (53,5 cm)
B: 11" -( 28 cm)
Alcove Installation
Fig. 12
Double wall pipe and stove heat shield
A: 55" - (140 cm)
B: 15" - (39,5 cm)
C: 21" - (53,5 cm)
D: 48" - (122 cm)
Alcove with rear heatshield
Fig.13
A: Min. 96" - (244 cm)
1
1
B: Max. 24" - (61 cm)
A
Fig. 14
Alcove - double wall pipe and
wall protection
A: 41" - (104 cm)
B: 8" - (20,5cm)
C: 14" - (36 cm)
D: 48" - (122 cm)
Alcove with wall protection
Fig. 15
A: Min. 96" - (244 cm)
B: Max. 48" - (122 cm)
C: Min. 41" - (104 cm)
D: 1" - (2,5 cm)
Parallel installation with wall shield
Fig. 16
Wall shield
• Must be 27" wide
and centered
behind the stove.
• Must be 1" off the
wall and 1" off the
floor.
• With single wall
pipe, the shield
must be 49" high
measured off the
floor.
• With double wall
pipe, the shield
must be 37" high
measured off the
floor.
Combustible wall
(Measurements in cm - for Canada)