High-Wall Type
F06
F07
F08
F10
F12
F13
F15
F29
F31
H01
H02
H03
H04
H06
L03
L07
L08
L09
39-EN
All manuals and user guides at all-guides.com
Outdoor unit temp.
ALT
sensor (TE/TS) error
ALT
TL sensor error
Outdoor unit outside
ALT
air temp. sensor error
Indoor unit room
ALT
temp. sensor (TA)
error
ALT
TS sensor error
Heat sink sensor
ALT
error
Temp. sensor
ALT
connection error
Indoor unit, other
SIM
P.C. board error
Outdoor unit P.C.
SIM
board
Outdoor unit
compressor
breakdown
Outdoor unit
compressor lock
Outdoor unit current
detect circuit error
Case thermostat
operation
Outdoor unit low-
pressure system
error
Duplicated header
SIM
indoor units
Group line in
SIM
individual indoor unit
Indoor group address
SIM
not set
Indoor power level
SIM
not set
– 39 –
Outdoor temp. sensors (TE/TS),
outdoor P.C. board --- Open-
Outdoor
circuit or short-circuit of the heat
exchanger temp. sensor was
detected.
TL sensor may be displaced,
Outdoor
disconnected or short-circuited.
Outdoor temp. sensor (TO),
outdoor P.C. board --- Open-
Outdoor
circuit or short-circuit of the
outdoor air temp. sensor was
detected.
Room temp. sensor (TA), indoor
P.C. board --- Open-circuit or
Indoor
short-circuit of the room temp.
sensor (TA) was detected.
TS sensor may be displaced,
Outdoor
disconnected or short-circuited.
Abnormal temperature was
Outdoor
detected by the temp. sensor of
the IGBT heat sink.
Temp. sensor (TE/TS) may be
Outdoor
connected incorrectly.
Indoor P.C. board --- EEPROM
Indoor
error
Outdoor P.C. board ---- In the
Outdoor
case of EEPROM error.
Current detect circuit, power
voltage --- Minimum frequency
was reached in the current
releasing control or short-circuit
Outdoor
current (Idc) after direct
excitation was detected
Wiring error of compressor (open
phase)
Compressor circuit ---
Compressor lock was detected.
Outdoor
Wiring error of compressor (open
phase)
Current detect circuit, outdoor
unit P.C. board --- Abnormal
Outdoor
current was detected in AC-CT or
a phase loss was detected.
Malfunction of the case
Outdoor
thermostat
Current, high-pressure switch
circuit, outdoor P.C. board --- Ps
pressure sensor error was
Outdoor
detected or low-pressure
protective operation was
activated.
Indoor address setting error ---
Indoor
There are two or more header
units in the group.
Indoor address setting error ---
There is at least one group-
Indoor
connected indoor unit among
individual indoor units.
Indoor address setting error ---
Indoor
Indoor address group has not
been set.
Indoor power level has not been
Indoor
set.
Installation Manual
Entire
stop
Entire
stop
Operatio
n
continue
d
Auto-
reset
Entire
stop
Entire
stop
Entire
stop
Auto-
reset
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop
Entire
stop