Brief Overview Of The Pictures On The Display - Siemens PolyCool CPS 40 Manuel D'installation Et D'utilisation

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Picture Display
1
Display segment test for about 5 s
2
Selection of the circuit
After selecting the circuit, select the following mode with +/- and press <OK> to
confirm.
3
CONF MODE (configuration mode)
4
REFRIG (selection of refrigerant)
5
ENABLE (Enabling/disabling the
compressor and EIV feedback signal)
6
CAP
7
SENSOR
8
RANGE (Measurement range of X4)
9
UNITS
Continously press <ESC> and back to picture 3
10
PARA MODE (parameter mode)
11
∆T
∆T SP
(setpoint of superheat)
(6.0 K / 10.8 °F default)
∆T XP
(P-band superheat)
(10 K / 18 °F default)
∆T TN
(integral action time superheat)
(30 s default)
∆T D
(D-part of superheat)
(0 default)
Continously press <ESC> and back to picture 10
12
CAP
CAP SMX (max. setpoint increase)
CAP SD
(SD=1 indicates that 0 V / 4 mA
corresponds to min. cooling capacity)
CAP SP
CAP XP
CAP TN
Continously press <ESC> and back to picture 12
48/124
Building Technologies
HVAC Products
8
Brief overview of the
pictures on the display
For the values of the setting variables and their increments,
refer to chapter 5.
(18.0 K / 32.4 °F default)
(external signal direction)
(setpoint of capacity control)
(6.0 °C / 42.8 °F default)
(P-band)
(35 K / 63 °F default)
(integral action time)
(5 s default)
CPS40
Procedure
Simutaneously press down +/-
buttons for at least 5 seconds.
Set with +/- and press <OK> to
confirm.
Press <OK> to confirm and proceed
In picture 3, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
Press <OK> to confirm and proceed
Press <OK> to confirm and proceed
In picture 11, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
Press <OK> to confirm and proceed
In picture 12, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
CE1U3372XX / H 74 319 0555 0 a