Picture Display
13
MOP
MOP SP
MOP XP
MOP TN
Continously press <ESC> and back to picture 13
14
SAFETY (safety control)
VD (Valve startup delay time)
(0 default)
VO (Valve startup opening limit)
(0 default)
PA (alarm delay of pressure sensor time when
compressor ON)
(5 s default)
TL (Low limit for temperature measurement)
(-40 °C / -40 °F default)
MI (Minimum superheat ∆T)
(2 K / 3.6 °F default)
Continously press <ESC> and back to picture 14
15
SIMU MODE (simulation mode)
16
MAN EIV (manual opening of the valve by means of
internal DC 0...10 V signal)
Caution! At your own risk!
May cause serious damage to the compressor!
17
EIV (the actual position of EIV to the manipulated
opening MAN EIV)
18
TO (actual value of evaporation temperature)
TOH (actual value of suction gas temperature)
Continously press <ESC> and back to picture 15
Building Technologies
HVAC Products
(Setpoint of MOP)
(15 °C / 59 °F default)
(P-band of MOP)
(5 K / 9 °F default)
(integral action time of MOP)
(30 s default)
CPS40
Procedure
Press <OK> to confirm and
proceed
In picture 13, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
Press <OK> to confirm and
proceed
In picture 15, set with +/-
Continue/confirm with <OK>
Exit with <ESC>
Press <OK> to confirm and
proceed
In picture 15, press <OK>
Exit with <ESC>
In picture 16, press <OK>
again.
In picture 17, set with +/-
CE1U3372XX / H 74 319 0555 0 a
22.09.2006
49/124