Building Technologies
HVAC Products
• Before soldering the valve into the pipework, the flow
direction must be carefully checked
• Make sure that all soldering material, copper grindings etc.
are removed from the pipework
• The valve body must be cooled with a wet cloth during the
soldering
• Mount a filter upstream to the valve
• The pipework must be fixed so that the valve connection
supports do not come under any mechanical load.
Vibrations can lead to pipework breaking!
• Evaporator temperature below 0 °C:
the valve body (incl.top/signal converter)and pipework
leading away from the valve must be isolated
• Evaporator temperature above 0 °C:
only the valve body and the pipes leading away from the
valve must be isolated (see picture).
Do not isolate upper part and electronics (overheating)!
Pressure sensor
Pressure sensor must be mounted upright over the
pipework
Can be mounted directly on the suction pipe
Temperature sensor
135°
The further the sensor is from the evaporator, the more
stable the control (max. 2 m).
It is recommended to increase the setpoint of superheat
accordingly.
CPS40
Mount as near as possible to the
evaporator outlet (max. distance 2 m /
6.5 ft) on a straight piece of pipework /
inmediately after or on the outside part
of an elbow
Fix with a cable tie
Isolate
CE1U3372XX / H 74 319 0555 0 a
22.09.2006