Electrical Data - Burkert 1062 Manuel Utilisateur

Masquer les pouces Voir aussi pour 1062:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Version with double
inductive switch (4-wire)
statuses detected
valve open and valve closed
valve open or closed
using lights and electrical signal via
indication mode
terminal block
colour of the lights
an orange light comes on when the
depending on the
valve opens and a red light comes on
status detected
when the valve closes
power up light
green
Version with double
inductive 2-wire NAMUR
switch
statuses detected
valve open and valve closed
valve open or closed
using lights and electrical signal via
indication mode
terminal block
colour of the lights
an orange light goes off when the
depending on the
valve opens and a red light goes off
status detected
when the valve closes
6.4.3.
General data specific to the devices
approved by csA
Pollution degree
2
Installation category
I
14
All manuals and user guides at all-guides.com
English
Type 1062
Technicaldata
Altitude max.
2000 m
Electric power
supplied by an SELV (Safety Extra Low
Voltage) source
6.4.4.

electrical data

Connection cable
standard, diameter between 5 and
7 mm, max cross-section of the strand
1 mm
Mechanical contact
version (per contact)
Power supply of
12-30 VAC or
devices approved by
12-48 VDC
CSA and CE
Power supply
12-30 VDC or
of devices only
12-48 VDC/VAC or
approved by CE
48/110 VDC/VAC or
110/250 VDC/VAC
Power consumption
< 35 mA (48 VDC)
< 8 mA (220 VAC)
Allowable load
depending on the power supply
voltage and the type of load, inductive
or resistive: see Table 1: next page
Type of output
contact normally open or normally
closed
2