Version with double
inductive switch (4-wire)
•
statuses detected
•
valve open and valve closed
•
valve open or closed
•
using lights and electrical signal via
indication mode
terminal block
•
colour of the lights
•
an orange light comes on when the
depending on the
valve opens and a red light comes on
status detected
when the valve closes
•
power up light
•
green
Version with double
inductive 2-wire NAMUR
switch
•
statuses detected
•
valve open and valve closed
•
valve open or closed
•
using lights and electrical signal via
indication mode
terminal block
•
colour of the lights
•
an orange light goes off when the
depending on the
valve opens and a red light goes off
status detected
when the valve closes
6.4.3.
General data specific to the devices
approved by csA
Pollution degree
2
Installation category
I
14
All manuals and user guides at all-guides.com
English
Type 1062
Technicaldata
Altitude max.
2000 m
Electric power
supplied by an SELV (Safety Extra Low
Voltage) source
6.4.4.
electrical data
Connection cable
standard, diameter between 5 and
7 mm, max cross-section of the strand
1 mm
Mechanical contact
version (per contact)
•
Power supply of
•
12-30 VAC or
devices approved by
12-48 VDC
CSA and CE
•
Power supply
•
12-30 VDC or
of devices only
12-48 VDC/VAC or
approved by CE
48/110 VDC/VAC or
110/250 VDC/VAC
•
Power consumption
•
< 35 mA (48 VDC)
< 8 mA (220 VAC)
•
Allowable load
•
depending on the power supply
voltage and the type of load, inductive
or resistive: see Table 1: next page
•
Type of output
•
contact normally open or normally
closed