3.3

Electrical connections

white
brown
green
yellow
Settings
4
Switching on and factory setting
4.1
After the supply voltage has been connected, the red LED signals
"Start-up" by flashing.
The factory setting is suitable for the following applications:
– Mounting height 4.0 to 4.9 m
– Relay hold interval 2 s
– Slow motion detection switched off
– Differentiation between people and vehicles active
– Crossing traffic optimisation switched off
– Detection of movements towards the detector (forwards)
The factory settings can be restored at any time using the remote
control (A+9)!
4.2
Establishing the connection to the remote control
Infrared interface
Numerical keys
to
1
9
Function keys
to
A
F
Start
G
Front side
Press key G on the remote control. If the connection has been established suc-
cessfully, G and one of the keys 1 to 7 light up (address of the detector).
If G flashes, the connection could not be established.
  Hold the remote control closer to the detector and point directly at it.
  Check the batteries in the remote control.
General:
Flashing keys on the remote control mean that the Herkules 2 has not
stored the programming that has been performed.
Steady lit keys on the remote control mean that the value has been
accepted and stored by Herkules 2.
4.3

Configuration mode

The connection between the remote control and Herkules can only be
established when the detector is in configuration mode. Configuration
mode is activated when the detector is switched on. This is deactivated
automatically 30 minutes after the last setting has been made.
Configuration mode can be activated by:
– Pressing any key on detector (x or y)
– Interrupting electrical power supply
– Via access code on remote control
Page 2
12–28 V AC / 12–36 V DC
12–28 V AC / 12–36 V DC
Relay 1
48 V AC / DC
55 VA / 24 W
grey
pink
Relay 2
blue
48 V AC / DC
55 VA / 24 W
red
Battery
compartment
Locking
screw
Rear side
Configuration mode can only be activated with the remote control if a
code has been stored previously (see access code).
1. Press start key G
  G and one of the keys 1...7 light up
2. Press C then 9
  C and 1 light up
  Access code function is switched on
3. Enter four-digit code 1111 - 9998
4. Press C
  C and 1 light up
  Configuration mode is activated
  Detector is ready for programming
  If C and 2 light up, code was incorrect
  Start again from step 1
4.4
Most important settings
1. Select enhanced level (C+1...8)
2. Set mounting height (F+4+1...7) if different from factory setting
Important: The detector will not function correctly if the
wrong mounting height is set
3. Set field size (D+1...9) if necessary using inclination angle, 0–90°,
in 15° steps
+
4.5
Displays on the detector
Start-up phase
Flashes several times during start-up, first slowly
Red LED
then quickly.
Configuration
Indicates the parameter (function no.) by the
Green LED
frequency of flashing.
Indicates the parameter level by the frequency of
Red LED
flashing.
Operation
Green LED
Lights up on detection, relay 2 is activated.
Green LED
Flashes on detection in the SMD field.
Red LED
Lights up on detection, relay 1 is activated.
Explanations
SMD = Slow Motion Detection
The slightest (quasi-static) movements are detected as soon as the
industrial door opens. The industrial door is only closed if no more
movement is registered during the set monitoring time.
CTM = Crossing traffic masking
Crossing traffic masking prevents an industrial door from being
inadvertently opened by objects that are only moving or walking past it
but do not want to pass through.
P/V identification
Using this function, it is possible to select whether the relay outputs
should be switched separately in response to people or vehicles (see
table of relay parameter settings).
+