Télécharger Imprimer la page

Ds308Ea Quad Passive Infrared Detector Installation Instructions - Bosch DS308EA Notice D'installation

Détecteur à infrarouge passif quad ts

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 5
DS308EA
Quad Passive Infrared Detector
Installation Instructions
Specifi cations
1
Input Power:
6.0 VDC to 15.0 VDC
25 mA @ 12.0 VDC
Standby
No internal standby battery.
Power:
Connect unit to DC power sources
capable of supplying standby
power if primary power fails. For
each hour of standby time needed,
25 mAh are required.
Coverage:
Broad (standard):
50 ft x 50 ft (15.3 m x 15.3 m)
Barrier (optional):
80 ft x 16 ft (24.4 m by 5 m)
Long Range (optional):
120 ft x 10 ft (36.6 m by 3.1 m)
Sensitivity:
Standard or Intermediate
Alarm Relay:
Form "C" normally closed (NC),
common (C), normally open (NO)
reed relay for silent operation.
Contacts rated at 3 W, 28 VDC,
125 mA maximum for DC resistive
loads. Protected by 4.7 Ω resistor
in common "C" leg of the relay.
Do not use with capacitive or
inductive loads.
Tamper
NC (with cover in place) tamper
Switch:
switch. Contacts rated at 28 VDC,
125 mA maximum.
Trouble
NC contact opens when the
Output:
detector is in a trouble condition.
Contact rated for 125 mA @ 28
VDC.
Anti-mask:
Anti-mask detection circuitry
with Spray Detect option senses
attempts to sabotage the detector
and provides a trouble output.
Temperature:
Storage and operating range is
-20°F to +120°F (-29°C to +49°C).
Options:
B328 Gimbal Mount Bracket, B335
Low Profi le Mount Bracket, B338
Ceiling Mount Bracket, TC6000
Test Cord, OMB77-3 Barrier
Mirror, and OMLR77-3 Long
Range Mirror.
Note: Misaligning the detector in
these brackets can reduce the
detector's range and increase the
dead zone area.
Pointability:
The mirror is adjustable from
+1° to -17° vertically and ±10°
horizontally.
6
Wiring
Terminal
Label
Function
Input power: Use at least a
1
(-)
22 AWG (0.8 mm) wire pair
between the unit and the
2
(+)
power source.
3
A
Alarm relay (NO)
4
A
Alarm relay (C)
5
A
Alarm relay (NC)
6
T
Tamper
7
T
Tamper
Memory input (refer to
8
M
Section 12 Other Features)
9
TR
Trouble
10
TR
Trouble
Note: Seal the wire entrance (5-11) with the foam
plug provided.
12
Other Features
Apply a control voltage on Terminal 8 to activate
Memory, Night Mode, and Walk Test (refer to Table 3).
The control voltage must be between 6 VDC and 18
VDC.
Use a supply voltage to apply a control voltage to
Terminal 8 (12-1).
Or, use a control panel or external DC power supply as
control voltage (12-2):
-
+6 VDC to +18 VDC = On (switch closed)
Day
Disables the alarm memory and allows
Mode
the LED (if activated) to operate
normally.
Memory
When the detector is in Night Mode, the
memory activates. The detector stores
an alarm for display when switched to
Day Mode.
Night
Enables the alarm memory and
Mode
disables the LED operation.
Walk
When the detector is in Walk Test
Test
Mode, the LED indicates the current
alarm status regardless of Switch 1's
setting (refer to Section 7 DIP Switch
Confi guration). A stored alarm displays
when the memory input is switched to
Day Mode.
2
Installation Considerations
Not suitable for outdoor use (2-1).
Never install the detector where the passive infrared
(PIR) is in constant alarm (LED on). The LED is off
when properly installed.
Point away from direct and indirect sunlight (2-2). Point
away from glass or other objects that rapidly change
temperatures (2-3, 2-4, and 2-5).
Do not install this detector where pets are present (2-6).
Mount the detector on a solid and vibration free surface.
Note: The detector does not detect through glass.
Warning!
Apply power only after all connections are made and
inspected.
Coverage Patterns
3
(3-1) Broad coverage top view
o
(3-2) Side view with mirror adjusted to –5
(3-3) Mirror segment to pattern reference with view of
front polished surface
(3-4) Optional mirror OMB77-3, barrier: Mirror segment
to pattern reference with view of front polished
surface
(3-5) Barrier coverage top view
(3-6) Side view with mirror adjusted to –2
o
(3-7) Optional mirror OMLR77-3, long range: Mirror
segment to pattern reference with view of front
polished surface
(3-8) Long range coverage top view
(3-9) Side view with mirror adjusted to –1
o
Optional: Peel back tab to remove mask (3-10) on
look-down zones O, P, and Q.
4
Mounting Considerations
1. Select a mounting location. Mount the sensor where
an intruder is most likely to cross the coverage
pattern (4-1).
2. Mount the detector 6.5 ft to 8.5 ft (2 m to 2.6 m)
above the fl oor (4-2).
3. Mount the detector with the terminal block at the top
(4-3) and the mirror at the bottom (4-4).
5
Mounting
1. Remove the cover. Insert a thin fl athead screwdriver
into the notch at the bottom of the cover (5-1) and
lift.
2. Loosen the printed circuit board (PCB) assembly
screw (5-2).
3. Push the PCB assembly (5-3) up towards the top of
the base until you hear a click.
4. Lift (5-4) the PCB assembly out of the base.
5. Use the base (5-5) as a template to mark the
location for the mounting screws.
6. Thread the wires through the wire entrance (5-6) on
the base.
6. Mount the base (5-5) using one of these options:
-
For surface or corner mounting, use the
appropriate mounting hole knockouts (5-7) and
the screws and anchors provided.
-
For optional bracket mounting, use the
appropriate knockout (5-8) and refer to the
installation instructions supplied with the
bracket.
10. Use the cable ties (5-9) for strain relief.
11. Insert the PCB assembly into the base and slide
the PCB assembly down (5-10) until you hear a
click.
12. Tighten the PCB assembly screw (5-2).
13. Place the cover on the detector.
Anti-mask and Spray Detection
11
Feature
Anti-mask and Spray Detection prevents accidental or
intentional blocking of the detector. This feature detects
an object placed near the detector or detects a foreign
substance sprayed on the detector.
Note: The Anti-mask feature is always on. To disable
this feature, cover the anti-mask transmitter (5-12) with
masking tape.
Table 3: Mode Switching
Control Voltage
Action
(Terminal M)
Turn on Night Mode and
On for more than 20 sec
Reset Stored Alarm
Turn off Night Mode and
Off
Reset Stored Alarm
On for more than 5 sec,
Turn on Walk Test
but less than 20 sec
13
Noise Voltage Verifi cation
Measure the detector noise level at the noise voltage
pins, found behind a metal fl ap on the circuit board
(5-13). Also use this feature to troubleshoot false alarms
caused by environmental changes. When verifying the
noise voltage, test each channels one at a time.
1. Connect a DC voltmeter to the noise voltage pins
using the Bosch TC6000 test cable opening (5-11).
2. Set the meter scale for VDC.
The base reference level for reading background
noise is approximately 2.5 VDC.
Installations in quiet environments result in a steady
reading between 2.4 VDC and 2.6 VDC.
7
DIP Switch Confi guration
(6-1) On
(6-2) Off
Switch
Feature
Description
1
LED
Operation
2
Sensitivity
Standard:
Mode
Minimizes false alarms
Tolerates environmental extremes
Not recommended for long-range or barrier
patterns
Intermediate:
Use where an intruder might cover only a small
portion of the protected area
Tolerates normal environments
Note: Shipped in Intermediate Mode.
3
Spray
High sensitivity: Use to sense foreign substances
Detect
sprayed on the detector.
Low sensitivity: Use to reduce false anti-mask
events.
4
Motion
Set the motion monitor time (refer to Section 10
Monitor
Supervision Features)
Note: The detector is shipped with the Motion
Monitor and 25-second Anti-mask features
disabled.
5
Anti-mask
Set the anti-mask timer (refer to Section 11 Anti-
Timer
mask and Spray Detection Feature).
8
Mirror Alignment
Note: Touching the mirror surfaces can reduce
performance.
Adjust the mirror vertically to set the maximum detection
range (distance) and mounting height. There are angle
adjustment markings on both sides of the mirror (8-1).
Slide the mirror forward or back until the angle adjust-
ment markings align with the markers on each side of
the frame.
Use the chart located inside the front cover (8-2) to set
the correct vertical angle.
Adjust the horizontal protection coverage during the
Walk Test (refer to Section 9 Walk Test).
X = maximum range
Y = mounting height
9
Walk Test
1. Replace the unit's cover. It must be in place before
testing the unit.
2. Wait at least 2 minutes after power up to start the
Walk Test. The LED lights for 1 to 2 minutes until the
detector stabilizes and no movement is detected for
2 seconds.
3. Watch the LED as you walk towards the edge of the
pattern. The LED lights at the outside edge of the
coverage range.
4. Repeat Step 3 from different directions until you
adequately verify the coverage pattern.
5. Adjust the mirror ±10
o
horizontally by rotating it from
side to side to ensure adequate horizontal cover-
age.
5. Adjust the mirror up and down, as needed, to en-
sure the coverage pattern is not too high or too low.
Note: To verify the detector clearly views the detection
area, instruct the end user to walk through the outer
edge of the coverage pattern daily. At least once a year,
check detector's the range and coverage.
It takes approximately 25 sec for the detector to react to
a masked or sprayed condition if the anti-mask timer is
on (refer to Section 7 DIP Switch Confi guration). If the
anti-masking circuitry activates, a supervision trouble
condition occurs. The Alarm/Test LED fl ashes three
times, and the trouble relay activates.
Recommendation: Set the anti-mask timer in situations
where false masking events such as dusting the
detector or removing and replacing the cover occur.
After 10 sec of inactivity, the trouble condition
automatically resets the next time the alarm activates.
Momentarily removing power from the detector also
resets the trouble condition.
The size of the anti-mask detection zone varies
depending on Switch 3's setting (refer to Section 7 DIP
Switch Confi guration).
(11-1) Anti-mask detection zone with Switch 3 (Spray
Detect) off.
(11-2) Anti-mask detection zone with Switch 3 (Spray
Detect) on.
(11-3) Keep-out zone: Do not mount the detector within
24 in. (60 cm) of moving objects such as doors,
cabinets, or curtains.
During the Walk Test, voltage changes greater than
0.75 VDC from the reference level indicate the
detector works correctly. If changes are less than
0.75 VDC, the device might fail to respond if the
temperature difference between the intruder and the
background is minimal.
3. Turn on all heating and cooling sources that
normally operate during times of protection.
4. Stand away from the unit outside the coverage
pattern.
5. Monitor the background noise for at least 3 min.
Readings should not deviate from the reference
level by more than ±0.15 VDC. For readings outside
these limits re-point the unit slightly, or mask the
affected zones.
Switch Position
ON: LED operates when
alarm is activated.
OFF: LED does not
operate on alarm.
ON: Standard
OFF: Intermediate
ON: High anti-mask
sensitivity
OFF: Low anti-mask
sensitivity
4 ON and 5 OFF: 30-day
motion monitor and 25-
second anti-mask timer on.
4 OFF and 5 ON: Motion
monitor off and 25-second
anti-mask timer on.
4 OFF and 5 OFF: Motion
monitor and 25-second
anti-mask off.
10
Supervision Features
The LED shows a supervision trouble condition at
the detector and indicates the cause of the trouble
using coded pulses. The trouble signal activates
the trouble relay on Terminals 9 and 10. The relay
can be connected to a 24-hour zone. Table 2
shows LED responses to the supervision features.
The supervision features are:
PIR
PIR operation is checked
electronically approximately
every 12 h. If the circuit fails,
the LED fl ashes four times and
activates the Trouble output.
Motion
Verifi es the detector clearly
Monitor
views the detection area.
Supervision
Select 30-day supervision
to monitor activity. If the
detector senses activity, the
timer resets. If no activity is
detected over 30 days, the
LED fl ashes two times and
activates the trouble output.
Refer to Section 7 DIP Switch
Confi guration.
Use Memory to count down
only during disarmed periods
(refer to Section 7 DIP Switch
Confi guration). The motion
monitor timer stops when
the control panel is placed
in the Armed (Night) Mode.
The timer resumes when
the control is placed in the
Disarmed (Day) Mode.
Trouble
An alarm activation resets
Reset
a motion monitor trouble
condition and an anti-mask
trouble condition. These
trouble conditions can also be
reset by temporarily removing
power. Wait 10 sec before
resetting the anti-mask timer.
Table 2: LED Responses to Supervision
Features
LED
Cause
On
Unit alarm
Two fl ashes*
Motion monitor time-out
Detector is covered or
Three fl ashes*
blocked
PIR self test failure
Four fl ashes*
(replace the detector)
* Indicates the number of times the LED fl ashes
per cycle.
Bosch Security Systems
130 Perinton Parkway
Fairport, NY 14450-9199
www.boschsecuritysystems.com
© 2004 Bosch Security Systems
30466L
Page 3 of 8

Publicité

loading