Function Settings - Mitsubishi Electric LGH-F300RVX2-E Notice D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Function settings

Address setting is required when connecting to City Multi and MELANS.
Setting the address
Use the following procedure when setting the address for dedicated
Lossnay.
(The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.)
(1) Remove the control box cover.
(2) Turn the address setting switch on the circuit board.
• SW12 indicates the tens digit and SW11 indicates the ones digit.
• The factory setting is "00".
Address setting switch
SW12 (Tens digit)
* When the address number has been changed, the data in the
memory is automatically reset.
Changing the function selection
switches (SW-2, 5 and 6)
Set the selection switches (SW-2 and 5) to perform the appropriate
function.
* All function except "Trial operation" and "Auto fan speed setting
without Lossnay or M-NET remote controller" can be set also from
the remote controller (PZ-62DR-E). If the function is switched later
using the remote controller, it operates according to the setting on
the remote controller.
(SW2)
OFF
ON
1
Trial operation
No. 28
Pulse input setting
2
No. 9
Delay start setting for air conditioner starting
3
No. 6
Indoor negative pressure setting
4
No. 7
Indoor positive pressure setting
5
No. 64
Fan speed for air volume "High" setting
6
No. 65
Fan speed for air volume "Low" setting
7
No. 5
Automatic recovery setting after power interruption
8
N/A
9
N/A
10
(SW5)
OFF
ON
1
No. 12
Monitor output setting
2
No. 17
Exhaust fan setting during air conditioner defrosting
3
N/A
4
N/A
5
6
No. 66
CO
sensor or BMS setting
7
2
8
When connecting the CO
9
N/A
10
DIP-SW6 is to identify the model for circuit board. When replacing to new circuit board, set the same setting as old one.
(SW6)
SW6-1 SW6-2 SW6-3 SW6-4 SW6-5 SW6-6
LGH-F300RVX2-E
OFF
LGH-F380RVX2-E
ON
LGH-F470RVX2-E
OFF
LGH-F600RVX2-E
ON
LGH-F940RVX2-E
OFF
LGH-F1200RVX2-E
ON
* Do not change from factory setting. If changed, please set as factory setting.
Address setting switch
SW11 (Ones digit)
sensor, Auto fan speed setting without Lossnay or M-NET system controller
2
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
Change the function settings from the
remote controller PZ-62DR-E.
Please refer to the Instruction book of PZ-62DR-E for how to set the
function settings.
Eng-14

Publicité

Chapitres

Table des Matières
loading

Table des Matières