Installation method (continued)
• One shielded wire is connected to TB5 S on the PCB on terminal.
Address setting is required. (Refer to function setting section.)
M-NET transmission cable:
Connect any of the City Multi indoor unit, or
Mitsubishi Electric Air-Conditioner Network
System (MELANS) - to the Lossnay.
• Connecting positions are different for the Remote Controller PZ-60DR-
E and PZ-52SF-E.
PZ-60DR-E:
Connect to TM4 1, 2 on the PCB. (See Section
connecting with Remote Controller (PZ-60DR-E)".)
PZ-52SF-E:
Connect to TB5 A, B on the same terminal block as for the
M-NET transmission wires.
• Securely connect the M-NET transmission wires to TB5 AB. (No-
Polar)
Type: (Shielded wire, CVVS / CPEVS)
Wire diameter: AWG 16 (1.25 mm
CAUTION
• Don't tighten screws on the terminal block with a torque larger
than 0.5 Nm. It may damage the PCB.
• Always use shielded wires only for the M-NET transmission wires,
and finish the shield properly.

Function settings

Address setting is required when connecting to City Multi, Lossnay remote
controller (PZ-52SF-E) and MELANS.

Setting the address

Use the following procedure when setting the address for dedicated
Lossnay.
(The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.)
(1) Remove the control box cover.
(2) Use a flatblade screwdriver to turn the address setting switch on the
circuit board.
• SA1 indicates the 10 digit and SA2 indicates the 1 digit.
• The factory setting is "00"
SA1
SA2
10 digit
1 digit
* When the address number has been changed, the data in the memory
is automatically reset.
Changing the function selection switches
(SW-2 and 5)
Set the selection switches (SW-2 and 5) to perform the appropriate
function.
* The function marked (*) above can be set also from the remote
controller (PZ-60DR-E). If the function is switched later using the remote
controller, it operates according to the setting on the remote controller.
10
"When
1
2
2
) to AWG 14 (2.0 mm
)
Address setting switch
When interlocking with Mitsubishi Free Plan air conditioner
• Incase of PZ-60DR-E
Air
Air
conditioner
conditioner
MA remote
M-NET transmission cable
controller
• Incase of PZ-52SF-E
Air
Air
conditioner
conditioner
MA remote
M-NET transmission cable
controller
When connecting to PZ-60DR-E and MELANS
• Connect the power feeding unit.
Power
(Optional)
MELANS
supply unit
M-NET transmission cable
* Limit the total length of transmission wires no longer than 457 yd (500
m). Limit the wiring length between Lossnay and the power supply
unit (Optional) or the outdoor unit no longer than 219 yd (200 m).
(SW2)
1
Trial operation
2
Pulse input setting *
3
Power supply/exhaust when operation starts *
4
SA fan fixed at Low speed *
5
EA fan fixed at Low speed *
6
Power supply ON/OFF *
7
Bypass ventilation priority at Automatic mode *
Setting for TM4 90 output
8
9
Supply Extra High/High *
10
Exhaust Extra High/High *
(SW5)
1
Delay setting *
2
Operation monitor output *
Exhaust fan stop during defrosting *
3
Exhaust fan at Low speed at outdoor air lower than 5˚F (-15˚C)
4
Auto restoration after power failure *
5
Filter maintenance indication setting *
Setting for TM3 67 output
6
7
}
Interlock mode setting *
8
9
Exhaust fan stop at outdoor air lower than 5˚F (-15˚C) *
10
Not used OFF: LGH-F300, F470, F600RX
1
Settings for pulse input
2
Switching to power supply/exhaust when operation starts
3
Switching to the multi ventilation mode
4
Power supply ON/OFF function (cannot be set when PZ-41SLB-E is used)
5
Bypass automatic ventilation priority setting *
Setting for TM4 90 output
6
7
Extra High/High switch setting
8
Set for delay operation at heating or cooling start-up
9
Operation output monitor
10
Exhaust fan stop during defrosting, exhaust fan Low speed operation at
outdoor air lower than 5˚F (-15˚C)
11
Settings for automatic recovery following power supply interruption
(cannot be set when PZ-41SLB-E is used)
12
Settings for filter cleaning (cannot be set when PZ-41SLB-E is used)
Setting for TM3 67 output
13
14
Settings for interlock mode
15
Exhaust fan stop at outdoor air lower than 5˚F (-15˚C) *
Lossnay
PZ-60DR-E
Lossnay
PZ-52SF-E
PZ-60DR-E
5
ON : LGH-F1200RX
5
*