Function settings (continued)
1
Settings for pulse input
Set as shown when connecting the pulse signal equipment from a
building maintenance system to an external input.
OFF
ON
SW2
2
No pulse input (factory setting)
2
Pulse input
2
Switching to power supply/exhaust when operation starts
This sets the fan to run forcibly for 30 minutes when operation starts to
ventilate the indoor area. After 30 minutes, the system switches to enable
fan speed adjustment from the remote controller. Use this setting if the
indoor air is contaminated at night when the system is shut down and you
desire to ventilate the indoor area quickly when operation is started in the
morning.
OFF
ON
SW2
3
Normal (factory setting)
3
Runs the fan forcibly for 30 minutes when operation starts.
3
Switching to the multi ventilation mode
This sets the ventilation system to in the case that ventilation balance in
accordance with the use environment and installation location is selected.
There are four possible setting modes.
OFF
ON
Mode
Power Ventilation
4
Normal (factory
5
setting)
4
Power Supply
5
SW2
4
Power Exhaust
5
4
Power Save
5
Ventilation
* When using the Remote Controller (PZ-60DR-E), operation of the Extra
Low fan speed button initiates the Extra Low fan speed operation both
at the supply (SA) and exhaust (EA) sides. Independent operation of the
supply (SA) or exhaust (EA) side is prohibited when it is set at the Extra
Low fan speed.
Power supply ON/OFF function (cannot be set when PZ-41SLB-
4
E is used)
Controls stop and start operation by turning the power supply (208-230 V)
for the Lossnay on and off.
OFF
ON
Mode
Off
Stop and start is performed according to
6
SW2
(factory setting)
SW5-4 settings when the power is on.
Operation possible by turning power on
6
On
and off.
Mode
Operation
Operation
The fan speed alternates between the
High (Extra high) and Low instead of the
remote controller setting.
Runs the exhaust fan (EA) at Low speed
constantly.
Alternates the supply fan (SA) speed
between the High (Extra high) and Low.
Runs the supply fan (SA) at Low speed
constantly.
Alternates the exhaust fan (EA) speed
between the High (Extra high) and Low.
Runs the supply fan (SA) and exhaust fan
(EA) at Low speed constantly.
Switches to the Power Save Ventilation
setting regardless of the remote
controller's High or Low.
Operation
5
Bypass automatic ventilation priority setting
Two thermistors in the Lossnay unit detect the indoor (RA) and outdoor
(OA) air temperatures and automatically select the "Lossnay ventilation"
or "Bypass ventilation". With this mode, however, priority is given to the
"Bypass ventilation".
* This setting reflects to the night purge operation condition.
OFF
ON
When outdoor temperature (OA) is 82.4˚F (28˚C) or higher within
24 hours, then Bypass ventilation starts by the comparison
OA and RA temperature. The lowest RA temperature of Bypass
7
operation is 75.2˚F (24˚C) (factory setting)
When the night purge is set by the remote controller PZ-
60DR-E, night purge operation starts at a temperature of
SW2
82.4˚F (28˚C) (within 24 hours).
When outdoor temperature (OA) is 62.6˚F (17˚C) or
higher within 24 hours, then Bypass ventilation starts by
the comparison OA and RA temperature. The lowest RA
7
temperature of Bypass operation is 66.2˚F (19˚C)
When the night purge is set by the remote controller PZ-
60DR-E, night purge operation starts at a temperature of
62.6˚F (17˚C) (within 24 hours).
6
Setting for TM4 90 output
OFF
ON
Operation monitor output
Corresponds to operation mode output (TM4 90) based
8
on SW5-2 setting. (factory setting)
Operation monitor output with delay function 1
Corresponds to operation mode output (TM4 90) supply
SW2
fan with following function.
• Starts the output (TM4 90) 10 seconds after supply
8
fan operates.
• Lossnay continues to operate for 3 minutes after
stopping the output (TM4 90)
Caution : Fan may be operating after turn off the switch of
the remote controller.
7
Extra High/High switch setting
Select this function when increased air volume is required or when the
duct piping is longer.
OFF
ON
9
Supply fan (SA) - High fixed (factory setting)
SW2
9
Supply fan (SA) - Extra High fixed.
10
Exhaust fan (EA) - High fixed (factory setting)
10
Exhaust fan (EA) - Extra High fixed
8
Set for delay operation at heating or cooling start-up
Delays Lossnay operation for 30 minutes when City Multi or Mr. Slim starts
operating or when a external device starts operating. (If the PZ-41SLB-E is
used, set it at the remote control. )
OFF
ON
1
No operation delay (factory setting)
SW5
Operation delay of 30 minutes
1
* This function is invalid with in 2 hours' restart
9
Operation output monitor
This setting is available when SW2-8 is OFF.
OFF
ON
Corresponds to operation mode output (TM4 90) exhaust
2
fan (factory setting)
SW5
Corresponds to operation mode output (TM4 90) supply
fan (The operation monitor output is off when the supply
2
fan is stopped for operation in cold regions or during the
City Multi or Mr. Slim defrost mode.)
Operation
Operation
Operation
Mode
Mode
11