Installation method (continued)
(2) Confirm that the pulse input switch (SW2-2) is set to "OFF".
(Set to "OFF" at time of shipment.)
Lossnay
Power supply
When using Mitsubishi Mr. Slim air conditioner with MA Remote
controller
Connect the interlocking cable connector side to CN2L on the circuit
board for the indoor Mr. Slim unit, then connect the lead wire side to
the 1 and 2 of the input terminal block (TM2) for the Lossnay external
controller input. (No polarity)
• Always separate the power supply cable and the Slim-Lossnay
connection cable by 2" (5 cm) or more to prevent the unit from
malfunctioning.
• The Slim-Lossnay connection cable is 9 7/8" (0.25 m) long. When wiring,
extend it as far as necessary.
Lossnay
External controller input (TM2)
Within 457 yd (500 m)
Note
• The Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E) cannot be
used with this system.
• Use MA remote controller of Mr. Slim for switching Lossnay ON/OFF
or the fan speed.
• The ventilation mode is "automatic ventilation".
• The Slim-Lossnay connection cable may be extended to a
maximum length of 457 yd (500 m). (Extension cable specifications
are as detailed below)
Ensure that all connections are secure and that the appropriate
insulation is provided.
Use extension cable sheathed PVC cable or cable AWG 20 (0.5 mm
2
to AWG 17 (1.0 mm
).
When the external device has a charged operating signal of 12
VDC or 24 VDC
• Connect the operating signal (wire) from the external device via the
remote output to 1 and 2 on the external control input terminal
block (TM2). (No polarity)
Lossnay External control input (TM2)
Overall connection extension length
(Follow the operation manual for the external equipment.)
When the external device has an uncharged a-contact signal
• Connect the operating signal (wire) from the external device via the
remote output to 1 and 3 on the external control input terminal
block (TM2).
8
Remote controller
(PZ-60DR-E or PZ-41SLB-E)
External device
Power supply
Operating switch
for external device
Slim-Lossnay connection
cable (Enclosed accessory)
CN2L
White
Mr. Slim (Indoor unit)
Red
Printed circuit board
2
AWG 20 (0.5 mm
) to AWG 17
2
(1 mm
) sheathed PVC cable
External device
12 or 24 VDC
CAUTION
• If an optocoupler or any other type of polar coupler is used at
the uncharged a-contact, connect the positive side to 3 and the
negative side to 1.
3
When interlocking with a pulse output device
(1) Move the pulse input switch [SW2-2] to the ON position.
(Refer to function settings
(2) Connect the pulse output device (i.e., building management system)
to the external control input terminal block [TM2].
• A pulse width of at least 200 msec will be needed.
• When using PZ-60DR-E, it can be set also from the remote controller.
Connecting methods vary depending on the types of pulse signal
2
Refer to Section
"When the external device has a charged operation
signal of 12 VDC or 24 VDC" or "When the external device has an
uncharged a-contact signal".
SW2
4
When operating multiple Lossnay units
(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units (7 units for F1200)
using a transmission cable (PVC insulated PVC jacketed and either
between AWG 22 (ø 0.65) and AWG 16 (ø1.2), or between AWG 22 (0.3
2
mm
) and AWG 16 (1.25 mm
(2) Change the setting on the main/sub switch (SW1) on the second and
subsequent Lossnay units to "Sub".
Lossnay (Main)
Power
supply
2
)
Lossnay (Sub)
Power
supply
Lossnay (Sub)
Power
supply
MAX 15 units
CAUTION
Don't tighten screws of terminal block with a torque larger than 0.5
Nm. It could damage the PCB.
Note
• Up to four AWG 22 (0.3 mm
wires can be connected to one input terminal.
• For other types of wire, up to two can be connected.
• The operation signal and pulse signal can be connected to the
external device of the main Lossnay only.
• Connect the power to each respective Lossnay unit.
• When LGH-F1200RX
5
even if extra low fan speed is selected.
Lossnay External controller input (TM2)
2
AWG 20 (0.5 mm
) to AWG 17 (1 mm
sheathed PVC cable
External device
Uncharge a-contact
Within 457 yd (500 m)
1
"Settings for pulse input".)
ON
1
2
3
4
5
6
7
8
9 10
ON
OFF
2
) in cross section).
Remote controller
Main/Sub selection switch
(PZ-60DR-E or PZ-41SLB-E)
(SW1)
Power
Main Sub
External
supply
device
Operating switch
(Factory setting: main)
for external device
First
Lossnay
TM4
1
2
Second
TM4
1
2
Lossnay
Transmission cable
2
) stranded wires or AWG 22 (ø 0.65) PVC
is connected, they operate at low fan speed
2
)
Connect
to remote
controller
(PZ-60DR-E)
Connect
to third
Lossnay