5. Function settings (continued)
Pre-heater output setting 1)
No.60
ON temperature
Set the outdoor temperature for Pre-heater output ON.
When detecting temp. becomes the setting or less, Pre-heater output
starts.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
N/A
60
-
-
-
-
-
-
-
-
Pre-heater output setting 2)
No.61
OFF interval
Set the Pre-heater output interval. Output stops according to the set
hours.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
N/A
61
-
-
-
-
-
-
LED usage setting for PZ-70CSW-E during
No.62
non operation
Wall mount type CO
sensor PZ-70CSW-E has LED which indicate
2
the concentration level.
It is possible to select lit or unlit during Lossnay unit is not operating.
Refer to the Installation manual of PZ-70CSW-E for more detail.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
N/A
62
-
-
No.64
Fan speed for air volume "High" input
Set the fan speed setting when receiving "High" signal from remote
controllers (e.g. remote controller of City Multi and Mr. Slim, Lossnay
simple remote controller) which have High/Low air volume.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
SW2-6
64
(Factory setting)
ON
Setting
Outdoor temp. for Pre-
check
heater output ON
0
32 ˚F (0 ˚C) or less
(Factory setting)
1
30 ˚F (-1 ˚C) or less
2
28 ˚F (-2 ˚C) or less
3
27 ˚F (-3 ˚C) or less
4
25 ˚F (-4 ˚C) or less
5
23 ˚F (-5 ˚C) or less
6
21 ˚F (-6 ˚C) or less
7
19 ˚F (-7 ˚C) or less
Setting
Pre-heater output OFF
check
interval
0
1 hr
(Factory setting)
1
2 hrs
2
3 hrs
3
4 hrs
4
5 hrs
Setting
LED usage setting for
check
PZ-70CSW-E
0
Unlit
(Factory setting)
1
Lit
Setting
Operating fan speed
check
0
DIP-SW priority
(Factory setting)
1
Fan speed 4
2
Fan speed 3
No.65
Fan speed for air volume "Low" input
Set the fan speed setting when receiving "Low" signal from remote
controllers (e.g. remote controller of City Multi and Mr. Slim, Lossnay
simple remote controller) which have High/Low.
DIP-SW
Setting
check
SW No.
Setting
-
-
OFF
SW2-7
(Factory setting)
ON
No.66
CO
sensor or BMS setting
2
According to the type of external input, set this item.
Lossnay changes fan speed according to input voltage to CN26 when
3rd party's CO
sensor or BMS is setting.
2
When connecting with PZ-70CSW-E or PZ-70CSB-E, refer to their
manuals for detail.
Do not set other than below settings.
* The function of [CO
control: No/Yes ] on PZ-62DR-E is not
2
applicable for this product. Do not change that setting.
Note
For LGH-F940 and F1200RVX2-E, PZ-70CSB-E can be installed
only in the lower unit. Lossnay unit controls its fan speed according
to the lower unit detecting CO
concentration of the upper unit is high, Lossnay does not change its
fan speed.
DIP-SW
Setting
check
SW No.
Setting
-
-
5-6 OFF
5-7 OFF
5-8 OFF
(Factory setting)
5-6 OFF
5-7 OFF
SW5-6
5-8 ON
SW5-7
5-6 OFF
SW5-8
5-7 ON
5-8 ON
5-6 ON
5-7 OFF
5-8 OFF
5-6 ON
5-7 ON
5-8 OFF
[Pattern Z]
Lossnay changes fan speed as the table below. (Connection
example: BMS (Building Management System))
Input voltage[VDC] Fan speed
0 - 1.0
1.5 - 2.5
3.5 - 4.5
5.5 - 7
8.5 - 10
When the input voltage is in-between, it will cause unstable operation.
Eng-23
PZ-62DR-E
Setting
Operating fan speed
check
Function No. Setting Data
0
DIP-SW priority
(Factory setting)
65
1
Fan speed 2
2
Fan speed 1
concentration. Even when actual CO
2
PZ-62DR-E
Setting
CO
sensor or BMS
2
check
setting
Function No. Setting Data
0
DIP-SW priority
(Factory setting)
No external fan speed
1
control input
3rd party's CO
2
(0-10 VDC equals to
0-2000 ppm)
66
BMS
4
Refer to pattern Z below
5
PZ-70CSW-E
7
PZ-70CSB-E
Fan speed changing from
Remote controller
-
Available
1
N/A
2
N/A
3
N/A
4
N/A
2
sensor
2