Télécharger Imprimer la page

baltur BTL 14 Notice D'instructions page 25

Publicité

Les langues disponibles

Les langues disponibles

Diagnostics of the cause of fault
After lockout, the red fault signal lamp remains steady on. In that condition, the visual diagnostics of the cause of fault according to
the error code table can be activated by pressing the lockout reset button for more than 3 seconds. Pressing the reset button again for
at least 3 seconds, the interface diagnostics will be activated. Interface di-agnostics works only if the AGK20... lockout reset button
extension is not fitted. For more detailed information, refer to Data Sheet N7614. The following sequence activates the diagnostics of
the cause of fault:
Fault position
On
EK
> 3 s
Red blink code of signal lamp (LED)
2 blinks ● ●
3 blinks ● ● ●
4 blinks ● ● ● ●
5 blinks ● ● ● ● ●
6 blinks ● ● ● ● ● ●
7 blinks ● ● ● ● ● ● ●
8 blinks ● ● ● ● ● ● ● ●
9 blinks ● ● ● ● ● ● ● ● ●
10 blinks ● ● ● ● ● ● ● ● ● ●
During the time the cause of fault is diagnosed, the control outputs are deactivated.
- burner remains shut down.
- The alarm signal AL "is on terminal 10 which is under voltage
The diagnostics of the cause of fault is quit and the burner switched on again by reset-ting the burner control.
Press the lockout reset button for about 1 second (< 3 seconds).
Fault position
Visual diagnosis
Flashing
Error code table
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
Error code table
Possible cause
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
Free
Extraneous light on burner startup
Free
Free
Too many losses of flame during operation (limi-tation of the number of repetitions)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
Time supervision oil preheater
Free
Wiring fault or internal fault, output contacts, o-ther faults
9 / 14
0006080871_201104
Fault position
Interface diagnosis
PC / analyzer
EK
> 3 s
E
N
G
L
Reset
EK
I
< 3 s
S
H

Publicité

loading

Ce manuel est également adapté pour:

Btl 20Btl 26