Step 3: Mount the Wallbox

1.  Mount a standard U.S. wallbox on a dry, flat indoor surface that is accessible and allows for system programming 
and operation. See the table below for the recommended wallbox for each model.
  Use a minimum depth of 2 3/4 in. (68 mm), preferably 3 1/2 in. (87 mm). Allow at least 4 1/2 in. (110 mm) 
clearance above and below the faceplate to ensure proper heat dissipation. Allow 1 in. (25 mm) for faceplate 
overhang on all sides. 
Control Unit Model
GRX-4102/4502 
GRX-4103/4503 
GRXSLD-4103/4104 
GRX-4104/4504 
GRX-4106/4506
GRX-4108/4508 
GRX-4116/4516
GRX-4124/4524 
GRXSLD-4106/4108
2.  Pull the PELV (CLass 2: USA) wiring into the wallbox using the rearmost 
knockouts. This will provide the most clearance when mounting the control 
unit. Use recommended cable as specified in "PELV (Class 2: USA) Cables" 
on page 3.

Step 4: Connect PELV (Class 2: USA) Cable to the Control Unit

GRAFIK Eye 4000 series control units use PELV (Class 2: USA) wiring to supply power and carry communications 
between the panels, control units, and wallstations. 
Important Wiring Information
• Lutron requires that you connect (daisy-chain) control units and wallstations with two twisted pairs for operation: One 
pair of #12 AWG (2.5 mm
•  Use properly certified PELV (Class 2: USA) cable. For a description of recommended cable types, refer to  
"PELV (Class 2: USA) Cables" on page 3.
• Install in accordance with all local and national electrical codes.
•  The control unit's low-voltage PELV (Class 2: USA) circuit is 24 V
To connect the PELV (Class 2: USA) wires to the control unit:
1.  Strip 1 in. (25 mm) of insulation from the PELV (Class 2: USA) 
cable in the wallbox.
2.  Strip 3/8 in. (9.5 mm) of insulation from each wire.
3.  Connect the twisted pair for low-voltage power wiring to terminal 
1 (common) and terminal 2 (24 V
NOTE: You will daisy-chain this low-voltage power wiring to 
wallstations and/or other control units. Refer to pages 8 and 9.
4.  Connect the twisted pair data link to terminal 3 (MUX) and 
terminal 4 (MUX) of the control unit.
NOTE: You will daisy-chain this data link to wallstations and/or 
other control units. Refer to pages 8 and 9.
5.  If shielded wire is used, connect the drain wires to each other 
or to terminal D on the wallstation, if present. Do NOT connect 
drain wires to earth/ground.
WARNING! Make sure no bare wire is exposed after 
making connections. The recommended installation torque 
is 3.5 in.-lbs. (0.4 N•m) for PELV (Class 2: USA) connec-
tions.
R
Wallbox size
2-gang wallbox*
3-gang wallbox*
4-gang wallbox
2 
) for the low-voltage power wiring, and one pair of #22 AWG (1.0 mm
) on the control unit.
*  Y ou may substitute two single-gang wallboxes for a 
2-gang wallbox, or three single-gang wallboxes for a 
3-gang wallbox.  
Single-gang wallbox (Lutron P/N 241218);  
4-gang wallbox (Lutron P/N 241400).
3.5 in. 
(87 mm)
3.75 in. 
(95 mm)
.
GRX-CBL-46L
GRAFIK Eye
 4000 Series Control Unit Installer's Guide     7
®
7.9 in. 
(200 mm)
2 
) for a data link.
PELV  
(Class 2: USA)  
cable
 1.0 in. 
3/8 in.
(25 mm)
(9.5 mm)
Terminal 1
Terminal 2
Terminal 3
Terminal 4
Drain/daisy chain
Emergency/daisy 
chain