Assign Link Hierarchy (2Link
Link hierarchy is used only when there are two control links. Each circuit can be assigned to a hierarchy listed 
below (see job prints if predetermined). If you are not sure if you have a 2Link circuit selector, please call Lutron 
Technical Support.
A. To view or assign the Link Hierarchy, press and hold 
buttons 2 and 5 until Select Value LED flashes twice 
repeatedly.
B. Press button 5 until the Circuit Level LED lights.
C. Use buttons 1 and 2 to choose circuit number.
D. Use buttons 3 and 4 to assign the Link Hierarchy (see 
Table for options).
  •  If Link Hierarchy A or b is selected, go to Step I.
  •  If Link Hierarchy A2 or b2 is selected, go to Step E.
  •    I f Link Hierarchy A1, b1, Ab1, or Ab2 is selected, go to 
Step G.
E.  Press button 5 until Load Type LED lights.
F.  Select Zone X.
  4000 Series on Secondary Link: Press button 3 or 4 to 
select both control unit and zone assignment. Example 
- If the control desired is addressed to 'A2' and the zone 
desired is the 3rd from the left, use buttons 3 and 4 to get 
'A23' as a value for the appropriate circuit.
  DMX512: Press button 3 or 4 to select zone assignment (1-512).
G. Press button 5 until the Zone Assignment w/Circuit Schedule LED lights.
H. Select the Secondary zone assignment.
  4000 Series on Secondary Link: Press button 3 or 4 to select both control unit and zone assignment. Example: If 
the control desired is addressed to 'A2' and the zone desired is the 3rd from the left, use buttons 3 and 4 to get 
'A23' as a value for the appropriate circuit.
  DMX512: Press button 3 or 4 to select zone assignment (1-512).
Note: Primary Zone assignment is covered on page 13 of this guide; if primary link is changed to B, repeat those 
steps to update your system.
I.  Repeat steps C and D for each and every circuit to be changed.
J.  Press and hold buttons 1 and 5 until VIEW VALUE LED lights.
Code
Definition
A
Link A only.
b
Link B only.
A1
Link A unless Link B is 
present.
A2
Link A unless Link B is present 
and Zone X intensity on Link B 
is >50%.
b1
Link B unless Link A is 
present.
b2
Link B unless Link A is present 
and Zone X intensity on Link A 
is >50%.
Ab1
Highest intensity of the zone 
assignments of Link A and 
Link B.
Ab2
Lowest intensity of the zone 
assignments of Link A and 
Link B.
14     GRAFIK Eye
 4000 Series Control Unit Installer's Guide 
®
only)
TM
1 2 3 4
1 2 3 4
S
ELECT
V
S
Link A
Link B
S
ELECT
Circuit Level
Load Type
Zone Assignment
Zone Assignment
Low-End Trim
High-End Trim
Address
Warning - Read instructions to set the Load
Type. Instructions show more load types.
Load Type Quick Reference:
--- Unassigned
Incandescent
1-1
2-1
Fluorescent Lutron Hi-lume
2-2
Fluorescent Lutron Tu-Wire
LINK 1
LINK 2
Primary 
Secondary 
Link
Link
A
None
b
None
A
b
A
b
b
A
b
A
A
b
A
b
D
5
C
Data A OK
Power OK
Data B OK
Link Link
A B
5
D
C
C
IRCUIT
1
2
Circuit
V
IEW
ALUE
V
ELECT
ALUE
3
4
Value
V
D
ALUE
ISPLAYED
5
(See Instructions)
w/ Circuit Schedule
w/ Zone Capture
TM
('Ad' displayed)
3-1
Neon / CC
Non-Dim
4-1
FDB Ballast
R
Ballast
TM
(Non-Ess)
(Essential)
Normal
Emergency
Application Example
Circuit to follow Link A (standard operation).
Panel is shared by two links to save on panel 
costs.
When the DMX-512 Stageboard is plugged in 
on Link B, listen to Link B. Return to Link A 
when the DMX-512 Stageboard is unplugged.
DMX-512 Stageboard is plugged in on Link B, 
but does not take control until the light intensity 
of Zone X on Link B is above 50%.
Redundant system. If Link A fails, circuits follow 
Link B.
DMX-512 Stageboard plugged in on Link B, but 
is not given control until the light intensity of 
Zone X on Link A is below 50%.
Redundant system. If Link A fails, circuits follow 
Link B.
Redundant system. If either Link A or Link B 
fails, the other will have higher intensities.
Energy management.
D
D
Step A:  
Press and 
hold Buttons 
2 and 5
R

Publicité

loading

Ce manuel est également adapté pour:

41004500