Télécharger Imprimer la page

Identify The Load Type For Each Zone - Grafik Eye 4000 Serie Mode D'emploi

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 85

Identify the Load Type for Each Zone

In a GRAFIK 4000 Series system, lighting load types are set using the circuit selector in the panel. For other load 
types (AC motors, Sivoia QED shades, and projection screens), the load type must be specified at the control unit. For 
all loads, setting the load type at the control unit changes the LED display for that load type (see below).
Set the load type for each zone
3
ZONE 5
ZONE 6
FADE
Zone LEDs
To set this load type:
Lighting Loads
Dimmable Loads 
Non-Dim (last on, first off) 
Non-Dim (first on, first off) 
Motorized Shades
AC Shades 
Blinking LED
Sivoia QED Shades 
Blinking  
LED
R
TEMPORARY
2
ZONES
M S
LS
Check for 
MASTER
1
Enter (exit) 
setup mode
Select this
LED display
To identify the load type for each zone:
1. Enter setup mode. Press and hold the SCENE 1 and 
OFF buttons for about three seconds, until the scene 
LEDs cycle.
2. Check for LS in FADE window. LS is the first code to 
display when you enter setup mode. In LS mode, ZONE 
LEDs turn on from top to bottom.
3. Set the load type for each zone. Press the ZONE 5 
4
,
or 6 button until the ZONE LEDs match the load type 
connected to each zone. Refer to the following table for 
each load type and its corresponding LEDs.
4. Exit setup mode. Press and hold the SCENE 1 and OFF 
buttons for about three seconds, until scene LEDs stop 
cycling.
In the sample 6-zone control unit shown here, Zone 5 is 
set for a dimmable load, and Zone 6 is set for non-dim 
(first on, first off).
Important Notes
  U se for any dimmable load. NOTE: This is the factory preset 
load type for each zone. 
  U se non-dim for any lights to be switched ON and OFF only—
not dimmed when fading between scenes. This load will be the 
last to switch on and the first to switch off.
  U se non-dim for any lights to be switched ON and OFF only—
not dimmed when fading between scenes. This load will be the 
first to switch on and the first to switch off.
  A C shades zones are factory set to unaffected in each scene. 
To program shade positions for a scene, refer to page 18. 
GRAFIK Eye 4000 control units must be addressed to control 
shades. To assign addresses, refer to page 16.
  S ivoia QED shade zones are factory set to unaffected in each 
scene. To program shade positions for a scene, refer to page 
18. GRAFIK Eye 4000 control units must be addressed to 
control shades. To assign addresses, refer to page 16.
GRAFIK Eye
 4000 Series Control Unit Installer's Guide     17
®

Publicité

loading

Ce manuel est également adapté pour:

41004500