4.1.1 CHimNEY CONNECTiON

Your chimney connector and chimney must have the same diameter as the appliance's exhaust flue outlet. The
appliance pipe must be made of aluminized or cold roll steel with a minimum 24 gauge thickness. It is strictly
forbidden to use galvanized steel.
A 6" (152mm) diameter single wall chimney connector, used to connect the appliance to the chimney, must be
installed with the crimped end toward the appliance. This will ensure that the moisture which condenses from the
burning wood will flow back into the fire chamber. Each joint in the chimney connector must be secured with at least
three sheet metal screws.
For installation of your chimney connector, the following recommendations may be useful.
The chimney connector must be short and straight. For optimum performance it is recommended that
all horizontal runs have a minimum 1/4" rise per foot (7mm per 305mm), with the upper end of the sec-
tion toward the chimney. For safe and proper operation of the appliance, see "INSTALLATION" instruc-
tions.
To insure a good draft, the total horizontal length of the connector should never exceed 8' (2.4m) to 10'
(3m). In the case of vertical installation, the total length of the connector can be longer and connected
without problem to the chimney at the ceiling level.
There should never be more than two 90° elbows in the entire connector and chimney system. Never
start with a 90° elbow. Always go up vertically for at least 2 feet (.61m) from the flue collar before using
a 90° elbow.
The connector must not pass through any combustible material, nor may it pass through a concealed
space (such as an attic, roof space, or closet). If passing through a wall, ceiling, or into a masonry
chimney, use either chimney components listed for that specific use, or means acceptable to local
authorities having jurisdiction over the installation.
This appliance must be connected to:
a.
A chimney complying with the requirements for
Type HT chimneys in the Standard for Chimneys,
Factory-Built, Residential Type and Building Heating
Appliance, or
b.
A code-approved masonry chimney with a fl ue
liner. Vent the stove into a masonry chimney or an
approved, insulated solid-fuel stainless-steel chimney
with as short and straight a length of 6" (152.4mm)
diameter chimney connector as possible. Connection
to a masonry chimney must be by a metal or masonry
thimble cemented in place.
TOWARD
APPLIANCE
58.1b
13
EN
MALE END OF
CONNECTOR
OR CHIMNEY
PIPE
FLUE GAS
DIRECTION
W415-1133 / A / 06.12.13