Antifreeze
Heat pump systems, which cannot be guaranteed to be frostfree,
should be equipped with a drainage option (see Fig.). The anti-
freeze function of the heat pump manager is active whenever the
heat pump manager and the heat circulating pump are ready for
operation. If the heat pump is taken out of service or in the event
of a power failure, the system has to be drained. The heating cir-
cuit should be operated with a suitable antifreeze if heat pump
systems are implemented in buildings where a power failure can-
not be detected (holiday home).

6.3 Electrical connection

A standard five-core cable is used for connecting the heat pump
to the power supply.
The cable must be provided by the customer. The conductor
cross section is selected in accordance with the power consump-
tion of the heat pump (see appendix Device information) and the
applicable VDE (EN) and VNB regulations.
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility blocking contactor or power contactor) as well
as a 3-pole circuit breaker with common tripping for all external
conductors must be installed in the power supply (tripping current
in compliance with the device information).
When connecting, ensure that the incoming supply has a clock-
wise rotating field.
Phase sequence: L1, L2, L3.
ATTENTION!
Ensure the rotary field is clockwise when connecting the mains cables (if
the rotary field is not clockwise, the heat pump will not work properly, is
very loud and may cause damage to the compressor).
The control voltage is supplied via the heat pump manager.
The heat pump manager has a 230 V AC-50 Hz power supply
and is connected in compliance with its own operating instruc-
tions (see heat pump manager operating instructions).
ATTENTION!
The control cable is essential for the operation of air-to-water heat pumps
for outdoor installation. The control cable and mains cable are to be
routed separately. It is not permissible for the customer to extend the
control cable.
www.dimplex.de
The control lines (not included in the scope of supply) have rec-
tangular plug connectors on both ends. One end is connected to
the heat pump manager, and the other end is connected to the
switch box in the heat pump. The plug connections to the heat
pump are located on the bottom of the switch box.
Three separate lines are used as control lines: One of the lines is
designed for the 230 V control voltage level, one for the signal
and/or extra-low voltage level and one is a bus cable for commu-
nication with the electronic expansion valve.
More detailed information can be found in the operating instruc-
tions of the heat pump manager.
For detailed information, see circuit diagrams in the appendix.
7

Start-up

7.1 General

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. These measures can also include an additional
warranty under certain conditions (see Warranty).

7.2 Preparation

The following items need to be checked prior to start-up:
All of the heat pump connections must be installed as de-
scribed in Chapter 6.
All valves that could impair the proper flow of the heating
water in the heating circuit must be open.
The air intake and air outlet paths must be clear.
The ventilator must turn in the direction indicated by the ar-
row.
The settings of the heat pump manager must be adapted to
the heating system in accordance with the manager's oper-
ating instructions.
Ensure the condensate outflow functions properly.
452163.66.36 · FD 9312
LA 6TU
EN-6