en | 10 | Installation and Operating Instructions | Bosch™ EV400 Series Charging Station

5.2 Applicable EU Systems

IMPORTANT
Identify the onsite service
connection before installing the EV400. If you are unsure of
the available service connection, consult the local utility
company.
The L1, L2, and Ground outputs (H, N for Europe) in the
following illustrations correspond to the inputs on the
EV400. For the (earth) ground connection, ground fault
protection is not possible unless the neutral (center tap on
the service transformer) is connected to an earth ground.
5.2.1
230V 3-Phase Wye Connection
230V 3-Phase Wye Connection (EU)
WARNING: Do not use more than one of
the three (3) phases and neutral in 230V
referenced-to-earth systems .
WARNING: The EV400 must be installed by a
licensed electrician and in accordance with
all local electrical codes, ordinances, and
authorities having jurisdiction .
WARNING: Do not install the EV400 near
flammable,
explosive,
materials. Do not locate or store flammable,
explosive, or combustible materials near the
EV400 .
5.2.2
Wall Receptacle Geometry
The drawing below represents the appropriate wall recep-
tacle in which the EU-version of EV400 plugs-in. This recep-
tacle is to be installed by a licensed electrcian.
YP-332 Receptacle (EU)
REV E | 02.19.2019
or
combustible

5.3 Applicable JP Systems

IMPORTANT
Identify the onsite service
connection before installing the EV400. If you are unsure of
the available service connection, consult the local utility
company.
The L1, L2, and Ground outputs (H, N for Europe) in the
following illustrations correspond to the inputs on the
EV400. For the (earth) ground connection, always connect
the neutral at the service panel to earth ground. Ground
fault protection is not possible unless the neutral (center
tap on the service transformer) is connected to an earth
ground.
5.3.1
200V Single Phase Connection
200V Single Phase Connection (JP)
WARNING: The EV400 must be installed by a
licensed electrician and in accordance with
all local electrical codes, ordinances, and
authorities having jurisdiction .
WARNING: Do not install the EV400 near
flammable,
explosive,
materials. Do not locate or store flammable,
explosive, or combustible materials near the
EV400 .
5.3.2
Wall Receptacle Geometry
The drawing below represents the appropriate wall recep-
tacle in which the JP-version of EV400 plugs-in. This recep-
tacle is to be installed by a licensed electrcian.
NEMA L6-30 Receptacle (JP)
or
combustible