1.25 Pump switch-on delay
Switch-on delay in seconds of the pumps after
the first.
IF CONTROL PANEL WITH INVERTER
SINCE 24A OR HIGHER, SET AT 10 s
1.26 Minimum H2O Pressure
Pressure value to be set according to the
pressure of the column of water on delivery.
1.27 Danger pressure
Set percentage of the maximum pressure
beyond which the control unit goes into excess
pressure alarm status
1.28 Maintenance Interval Pumps
Total running hours to be reached before
performing maintenance on Pumps
1.29 Pump rotation interval
Time of daily change in the pump starting
order.
0h: No change.
1-24h: Change according to the set time.
25h: Change at each restart or by remote
control.
1.30 Ramp start
Set in seconds of time alignment of the set
pressure set by the run command.
IF
CONTROL
PANEL
INVERTER SINCE 24A OR HIGHER,
SET AT 5 s
1.31 Running hours.
Page displaying the total running hours of the motors.
1.32 Starts per hour
Maximum threshold starts in an hour.
0: Alarm disable
1-60: Max number of starts per hours
1.33 Setting default
Page to restore the default data in all parameters of the board.
To restore the data press simultaneously the buttons 'increase' and 'decrease'.
0 - 100 s
0.0 - 2.0 bar
0 – P Nom.
0 - 99999 h
0 - 25 h
000 - 300 sec
WITH
0 - 60
53
5 s
(10s)
0.5 bar
P.Nom. Bar
10000 h
25 h
001 s
(005 s)
0