Interrupteurs de sécurité de 30 à 1 200 a

Publicité

Les langues disponibles

Les langues disponibles

s
SAFETY SWITCH MAINTENANCE INSTRUCTIONS
For use with: 30-1200 Amp Type VBII Safety Switches
Danger
Hazardous Voltage.
Will cause death or
serious injury.
Turn off and lock out all power supplying this
equipment before working on this device.
Replace all covers before power supplying
this device is turned on.
400-600A Fuse Clip
800-1200A Bolt-On Type Fuse Clip
Apply thin coat
of Nyogel 760G
to shaded area
of fuse
Technical Support: Toll Free: 1-800-241-4453
Subject to change without prior notice.
Siemens Industry Inc., Norcross, GA 30092
© Siemens Industry Inc. 2019
Peligro
Tensión peligrosa.
Puede causar la muerte o
lesiones graves.
Desenergice totalmente el equipo antes de
instalar o darle servicio. Reemplace todas
las barreras y cubierta antes de energizar el
interruptor.
Apply Nyogel
760G to shaded
area of fuse clip
Apply Nyogel
760G to shaded
area of fuse clip
spring
5. To Re-Energize Switch
With the switch handle in the OFF position:
15.1 Reconnect any cables or accessory leads
disconnected in step 2, Safety Precautions.
15.2 Replace all covers and shields.
15.3 Close and latch the door.
15.4 Turn OFF all downstream loads.
15.5 Turn ON power supplying the switch.
15.6 Turn ON the switch.
15.7 Turn ON all downstream loads.
Internet: www.usa.siemens.com/powerdistribution
4 / 4
Danger
Tension dangereuse.
Danger de mort ou risque de
blessures graves.
Mettre hors tension et cadenasser l'alimen-
tation avant d'intervenir sur cet appareil.
Remettre tous les couvercles en place avant
de remettre cet appareil sous tension.
I.L. No. R500634A01