Manual BVS 20 ATEX E 103 X / BVS 20 ATEX E 104 X
No. of single- or multicore conductors
Minimum distances of terminals blocks
from wall in the case of
Conductor
cross
1 conductor
section
2
[mm
]
1.5
20 mm
2.5
20 mm
4
20 mm
6
20 mm
10
25 mm
16
30 mm
25
40 mm
35
50 mm
50
60 mm
70
75 mm
95
100 mm
120
125 mm
150
140 mm
185
150 mm
240
160 mm
Table 3:
Minimum clearance between terminal blocks
and enclosure wall as a function of the num-
ber of conductors entering the enclosure
4.3
Cable and conductor entries
For type SAnR explosionproof switchgear
assemblies, only those cable and conductor
entries and plugs that possess an EU type-
examination certificate (Category 3G according
ICE Equipment Protection Level Gc) issued by a
European Notified Body as per IEC 60079-0,
IEC 600079-7 or IEC 60079-15 may be used.
Cable and conductor entries may only be fitted
in specially prepared holes that are closed off
with plugs.
The cable and conductor entries must be
installed so as to prevent self-loosening and
ensure permanent sealing of the cable and con-
ductor entry points.
The spacing between the cable glands is such
that a torque wrench can be used to secure the
gland bodies of the cable and conductor entries
in the enclosure wall and to tighten the seals aro-
und the cables.
In the factory the cable and conductor entries are
Edition February 2021
Copyright
brought in
2 conductors
3 or more
conductors or
2 side by side
20 mm
20 mm
20 mm
20 mm
20 mm
25 mm
25 mm
30 mm
30 mm
40 mm
40 mm
50 mm
50 mm
60 mm
60 mm
75 mm
75 mm
100 mm
100 mm
125 mm
125 mm
140 mm
140 mm
150 mm
150 mm
160 mm
160 mm
170 mm
170 mm
180 mm
13
thuba Ltd., CH-4002 Basell
Switzerland