Use Of Extension Cords - Wacker Neuson GP2500A Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operation
4.11

Use of Extension Cords

When a long extension cord is used to connect an appliance or tool to the
generator, a voltage loss occurs—the longer the cord, the greater the voltage loss.
This results in less voltage being supplied to the appliance or tool and increases
the amount of current draw or reduces performance. A heavier cord with a larger
wire size will reduce the voltage loss.
Damaged extension cords can cause electrical shock, resulting in serious injury or
death. DO NOT use worn, bare, or frayed cords. Replace damaged cords
immediately.
Use the chart below as a guide for selecting proper cable size.
Current
(Amps)
2.5
7.5
10
15
20
Use only extension cords rated for outdoor use and equipped with a
third-wire ground.
NOTICE: Operating equipment at low voltage can cause it to overheat.
Load in watts
120V
240V
300
5
600
900
1200
1800
2400
Maximum cable length in feet
#10
600
1000.
1200
500
1800
350
2400
250
3600
150
4800
125
34
#12
#14
600
375
300
200
200
125
150
100
100
65
75
50
wc_tx004573gb.fm
GP
#16
250
125
100

Publicité