Set-UP

6.1 General Information

The device is designed to enable several connection options.
The position of the air outlet opening can be moved from right
(factory default) to left or top by turning over one of the two
screwed on covers.
By replacing the bottom side cladding sections, it is also possi-
ble to move the hydraulic connection from left (factory default)
to right. The different connection options (see cap. 1) are
shown in the dimension drawing.
The air-to-water heat pump must be installed in a frost-free, dry
room on an even, smooth and horizontal surface. The entire
frame should lie directly on the floor to ensure an adequate
soundproof seal. If supporting feet are used, the heat pump
must be installed horizontally. In this case, the specified sound
level can be up to 3 dB(A) higher, and additional sound insula-
tion measures may be necessary.
The heat pump must be installed so that maintenance work can
be carried out without being hindered. This can be ensured by
maintaining a clearance of 1m in front of the heat pump and to
the side on which the heating water connections are located.
The side panel assemblies must not be covered by connecting
pipes.
0,1 m
1 m
(0,11 m)
1 m
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.
Never install the device in rooms subject to high humidity. Con-
densation can form on the heat pump and air circuit if the hu-
midity exceeds 50 % and the external temperature is below
0 °C.
If the heat pump is installed on an upper storey, the load-bear-
ing capacity of the ceiling should be checked. On account of
the acoustics, measures for isolating possible vibrations should
also be very carefully planned in advance as well. Installation on
a wooden floor is not recommended.
EN-6

6.2 Condensed Water Pipe

Condensed water that forms during operation must be drained
off frost-free. To ensure proper drainage, the heat pump must
be mounted horizontally. The condensate pipe must have a
minimum diameter of 50 mm and must be fed into a sewer in
such a way that it is safe from frost. Do not discharge the con-
densate directly into clearing tanks or cesspits, as aggressive
vapours or a condensed water pipe which has not been laid in a
frost-free manner could destroy the evaporator.

6.3 Sound

7
7.1 General Information
The following connections need to be established on the heat
pump:
0,11 m
- Fresh and exhaust air
(1 m)
- Flow and return flow of the heating system
- Condensate outflow
- Voltage supply
- Temperature sensor
452160.66.74 · FD 9912
We recommend connecting the heat pump to the heating
system using a flexible hose to prevent solid-borne noise
transmission to the heating system if requirements regard-
ing noise are high.
Installed air ducts should be sound-isolated from the heat
pump to prevent the transmission of solid-borne sound to
the ducts.
If the transport restraint screws are not removed from the
compressor, acoustic emissions from the device are signif-
icantly louder!