The Installation Of The Rear Panel; Debugging - Gree GMV-N22G/A3A-K Manuel D'utilisation

Table des Matières

Publicité

Multi Variable Air Conditioners Wall Mounted Type Indoor Unit

4.2 The installation of the rear panel

(1) Find the horizontal position by the seton method; since the drainage pipe is on the left
side, it is necessary to adjust the rear panel to make its left side a little bit lower.
(2) Fix the rear panel on the wall by bolts.
(3) After installing the rear panel, pull it by hands to check if it is secured enough. The hang
panel should support the weight of an adult (60kg), and the weight shared by every bolt
should be fairly even.
(4) The diameter showed in Fig.4.2 is 65mm.

4.3 Debugging

Setting of main indoor unit must be done after finishing installation of unit. Otherwise, the
whole system will report "L7" error and the whole unit cannot operate.
The indoor unit defaults to be slave indoor unit when ex-factory. During project debugging, if
master indoor unit hasn't been set manually, the outdoor unit will appoint one indoor unit as the
master indoor unit automatically. Then you can reset the master indoor unit by remote controller or
wired controller.
4.3.1 Setting by remote controller
Point the remote controller at the light board or wired controller
In fan mode, set master mode indoor unit through ▲ and ▼ button:
(1) Adjust set temperature to 30℃.
(2) Within 5 seconds, press ▼ button and then press ▲ button repeatedly for three times.
After finishing setting, "UC" is displayed on receiver light board for 5 seconds and "MASTER"
icon is displayed on wired controller.
4.3.2 Setting by wired controller
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.