From this new page you can manage:
• Setp Byp.
"By-pass" function activation depends on the "Setp Byp"
temperature. "Setp Byp" is selectable into a variable range
between: 15°C & 30°C (default value = 18°C).
• Lifetime (NO UK)
Is shown the duration of Filters Pre-Alarm.
(See "Pre -alarm: Filters checking"):
- Markets NON UK = after 3 or 6 or 12 months;
• Reset Fil
In case of Filters replacing, you need to reset the Filters Timer
manually:
- select [YES] to reset;
- select [NO] to not resect.
• Modbus ID
In the presence of another installed remote user interface, you
can configure a different address than the default one (which is
"1").
• Speed
See Fig. 3
From "Installer menu" page, selecting "Speed", you can join to
"Setting speed". Here, you can set motorfan speeds:
(C) Clean air outlet inside the room;
(D) Stale air outlet to outside.
For more details on setting "Speed", See:
"Setting Speed Menu".
• Language
Language selection
• No Frost
From "Installer menu" page, selecting "No Frost", you can join to
"Setting No Frost Menu". From this new page, is now possible to
choose desidered "No Frost functions" during the "No Frost"
process. For more details on setting "No Frost functions", See:
"Setting No Frost Menu".
SETP BYP.
018
LIFE TIME
3
RESET FIL
YES
MODBUS ID
001
SPEED
VSUP1
VEXH1
VSUP2
VEXH2
VSUP3
VEXH3
VSUP B
VEXH B
LANGUAGE
ENG
NO FROST
UN-BALAN.
HEATER
HEAT FORC
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
33