Replacing bonnet for quarter turn stop valve
Bonnet for quarter turn stop valve DN 20
Art. No.: 3692102000
Bonnet for quarter turn stop valve DN 25
Art. No.: 3692102500
1
Danger!
Disconnect the system from the power supply!
2
Shut off water supply.
3
Dismantle the servo drive.
(see Section 9)
Art. No.: 3691600100
4
Replace the bonnet from quarter turn stop valve.
5
Before installing the new bonnet, grease the EPDM jacket slightly
with suitable valve grease.
Install the new quartner turn stop valve bonnet in the reverse order.
During installation, it is important to make sure the valve is guided
correctly.
6
Install the servo drive and quarter turn stop valve in valve
position „closed".
(see Section 9)
Art. No.: 3691600100
7
Open the water supply. Press the release button, open the quartner
turn stop valve and check the connections for leaks.