Replacing Pump - Kemper FK-5 Instructions D'entretien

Masquer les pouces Voir aussi pour FK-5:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 30
EN
2
1

Replacing pump

Pump 3HM04P for DN 20
Art.-No. 3691102000
Pump 5HM05P for DN 25
Art.-No. 3691102500
i
This work may only be carried
out by a qualified electrician!
1
Danger!
Disconnect the system from the power supply!
2
Shut off the pressure line.
Drain reservoir.
Unscrew the drain valve.
Info
If necessary remove the container cleaning kit.
3
Loosen the screw connection on the suction and pressure line.
Note!
Water leak!
4
Loosen the Allen bolts below the pump and thus release
the pump.
18 /88 – K41003690008-00 / 04.2022 – © www.kemper-olpe.de
5
Pull the pump forwards.
6
Open the motor terminal board.
7
Disconnect the pump cables.
Brown wire
Terminal L
Blue wire
Terminal Z2/U1
Yellow-green wire Earth terminal
8
Loosen the cable gland and pull out the pump cables.
9
Take out the pump and dismantle the vibration absorber.
10
To install the pump, proceed in the reverse order.
11
If necessary, vent the pump (see installation instructions,
Section 28).
12
Check the system for correct functioning.